8
…2
CONTROL CONFIGURATION LEVEL
2.3
Ramp/Soak Profile Program
Page Header – Profile Program.
To advance to the
CONTROL CONFIGURATION LEVEL
frame press the
switch.
Select Program
Select the program to be configured:
Ch1–1
to
Ch1–10
–
Channel 1 programs 1 to 10
Ch2–1
to
Ch2–10
–
Channel 2 programs 1 to 10 (if available)
NONE
–
no program selected
Program Begin
Select the program start segment, between 1 and 99.
Program End
Select the program end segment between, 1 and 99.
Select Segment
Select the segment to be programmed (1 to 99).
When all segments have been programmed, select 0 to advance to
Repeat Program
frame.
Segment Start Value
Set the segment start value. The segment start value can only be set if it is the first segment of
a program.
A
Ramp
has different start and end set point values. A
Soak
has the same start and end set point
values. Adjacent segments of different
Ramp
or
Soak
programs MUST have the same start and
end values, unless an intermediate ‘spacer’ segment is used.
Segment End Value
Set the segment end value.
If segment start/end values are the same (Soak), advance to the
Soak Time
frame. If segment
start/end values are different (Ramp), advance to
Ramp Rate
frame.
Soak Time
Set soak time duration required, between 0 and 999.9.
The time units (hours or minutes) are configured in
Ramp/Soak Time Units
frame,
Profile Control
Page
.
Ramp Rate
Set the ramp rate.
The ramp rate is entered as the number of engineering units that change during the time period
(hours or minutes) configured in the
Ramp/Soak Time Units
frame,
Profile Control Page
.
Example – if a ramp of 10
°
F at 2
°
every minute is required, the ramp rate value entered is 2.0 (in
the minutes time base).
Ramp rates set excessively low over a wide range cannot be displayed properly at the
Current
Profile Segment
(
Time Remaining
) frame. This display shows a maximum of 999.9 units of time.
The display is decremental when the time remaining is less than 999.9.
Continued on next page.
•
Ramp/Soak
PrOFLE
PrOGrM
NONE
Ch1–1
PG–bEG
ENd
–.–
tIME
––
–––.–
StArt
NONE
PrOGrM
Ch2–10
Channel No.
Program No.
PG–ENd
SEGMNt
SOAK
rEPEAt
––––––
RAMP
rAtE
––––
––
––
––