![background image](http://html1.mh-extra.com/html/abb/com600-series/com600-series_product-manual_3381037012.webp)
ABB
12
Station Automation
COM600
Product version: 3.4
1MRS756764 B
Table 6. Inspection of mechanical structure
Description
Standard
Markings and mechanical structure According to IEC 60255-5, -6
Degree of protection by enclosure
According to IEC 60529
Clearance and creepage distances According to IEC 60255-5
Table 7. Power supply and module tests
Description
Standard
Auxiliary voltage
According to IEC 60255-6
Aux. voltage interruptions
According to IEC 60255-11
Ripple in auxiliary DC voltage
According to IEC 60255-11 12%, f = 2 x fn
Power consumption
According to CE EN 61010
Table 8. Insulation tests
Description
Standard
Dielectric test
According to IEC 60255-5
2 kV, 50 Hz for 1 minute
Impulse voltage test
According to IEC 60255-5
5 kV, 1.2/50 μs, 0.5 J
Insulation resistance
According to IEC 60255-5
>100 MΩ, 500 Vdc
Protective bonding impedance
According to IEC 60255-27
<0.1 Ω.
Table 9. Electromagnetic compatibility tests
The EMC immunity test level meets the requirements listed below:
Description
Standard
1 MHz burst disturbance test
• Common mode
• Differential mode
According to IEC 61000-4-18
and IEC 60255-22-1
2.5 kV
1.0 kV