Table 3.5.8.11-2 Configurable DPS properties for External OPC clients, subtype
OPEN_CLOSED_ITEMS
Description
Value or Value range/ Default
/Example
Property/Para-
meter
Basic
61850-Type
DPS
61850-Type
OPC item path for closed
Closed OPC Item
Path
OPC tem path for open
Open OPC Item
Path
Object subtype
OPEN_CLOSED_ITEMS
Sub Type
Defines the requested shortest interval in
milliseconds at which the source OPC
server should report that an OPC item’s
value has changed.
0 - 65535
Default: 0
Update Rate
Scale and Unit
Lookup Table Scale
Stepwise Linear Scale
Default: None
ClosedScale
Lookup Table Scale
Stepwise Linear Scale
Default: None
Scale
Controllable integer status (INC)
3.5.8.12.
Table 3.5.8.12-1 Configurable INC properties for External OPC client
Description
Value or Value range/ Default
/Example
Property/Para-
meter
Basic
61850-Type
INC
61850-Type
OPC item path for control
Control OPC Item
Path
OPC item path for state
State OPC Item
Path
Object subtype
Basic
Sub Type
Defines the requested shortest interval in
milliseconds at which the source OPC
server should report that an OPC item’s
value has changed.
0 - 65535
Default: 0
Update Rate
50
1MRS757274
Station Automation COM600 3.5
External OPC Server User's Manual
Summary of Contents for COM600 3.5