![ABB COM600 3.5 User Manual Download Page 31](http://html.mh-extra.com/html/abb/com600-3-5/com600-3-5_user-manual_3045562031.webp)
Description
Value or Value range/ Default
/Example
Property/Para-
meter
OPC item path for phase B
Phase B OPC Item
Path
Bitmask for phase C
0 to 65535
Default: 0
Phase C Bitmask
Defines the type of used bitmask for Phase
C
BITMASK_OR
BITMASK_AND
BITMASK_XOR
BITMASK_BOOL_ALL
BITMASK_BOOL_NONE
BITMASK_BOOL_ANY
BITMASK_BOOL_ANYNOT-
SET
BITMASK_BOOL_SOMENOT-
SET
BITMASK_BOOL_ONLY
BITMASK_BOOL_EXACTLY
Default: BITMASK_OR
Phase C Bitmask
Type
OPC item path for phase C
Phase C OPC Item
Path
Protection activation information (ACT)
3.5.8.3.
Table 3.5.8.3-1 Configurable ACT properties for External OPC Clients, subtype
Basic
Description
Value or Value range/ Default
/Example
Property/Para-
meter
Basic
61850-Type
ACT
61850-Type
Object subtype
Basic
Sub Type
Defines the requested shortest interval in
milliseconds at which the source OPC
server should report that an OPC item’s
value has changed.
0 to 65535
Default: 0
Update Rate
Paths
31
Station Automation COM600 3.5
1MRS757274
External OPC Server User's Manual