S M ART T EMP ER ATUR E MONITORI NG R EL AYS
STATUS
Approved
SECURITY LEVEL
Public
DOCUMENT ID.
2CDC112285M0201
REV.
B
LANG.
en
PAGE
19/42
© Copyright 2020 ABB. All rights reserved.
4.1.6.
Factory 6: Transformer supervision with PTC
Profile 6 follows the same logic as profile 5 with PTC sensors. In this setting each
measuring input corelates to one output relay: channel 1 to Relay 1, channel 2 to
relay 2 and channel 3 to relay 3. The temperature thresholds depend on the se-
lected sensors.
Cyclic switching function 1 is assigned to relay 2.
Relay 2 trips in case of sensor error for all measuring circuits.
Relay 1 and 3 operate in normally-open working principle, relay 2 in normally-
closed. Automatic reset is active for all output relays.
The operating logic and the settings are displayed in the block diagram for de-
tailed information: