4.1.1.
Factory 1 - Motor protection with PT100 sensors
This profile allows motor supervision with two escalation steps. The first thresh-
old is configured as a pre-waging at 130 °C for all measuring circuits. When the
threshold is reached, relay 1 will trip. The second threshold controls the switch
off at a temperature of 150 °C. Relay 2 will trip if the threshold value is measured
by any of the three measuring circuits. In case of sensor errors in any of the
three sensor circuits (short circuit, open wire) relay 3 is triggered immediately.
The relays energize when the measured temperature is below the threshold and
the set hysteresis value. The hysteresis is set to 10 K for the pre-warning and 5 K
for the switch off threshold.
The relays operate in closed circuit principle. Automatic reset is active for all out-
put relays.
The operating logic and the settings are displayed in the block diagram: