reset is selected. With a rotate action section 2 will be entered. A frame will be
displayed around the first relay and the trip reason for this relay will be displayed
in the bottom line.
The device offers two reset options: automatic and manual reset. To reset a relay
manually when manual reset is enabled the push-rotate button needs to be
pressed when the frame is around the relay which should be reset.
The reset screen will open:
By clicking on
a reset is conducted. To abort the reset and go back to the start
screen
needs to be selected.
Default setting for all relays is automatic reset. In this case the re-
set menu will not be displayed. If manual reset is configured for a
relay, the reset menu will become available automatically. The re-
lay detects if the reset condition is reached. In case it is not
reached the reset menu will not be available.
Example: In the picture displayed above, channel 1 shows a measured temperature
of 180.6 °C. Navigating the frame to relay 1 shows that it has tripped because the
configured threshold for overtemperature monitoring at 175 °C at channel 3 has
been reached.
Section 4
is used for devices with Modbus only. Here a symbol signalizes the work-
ing Modbus communication.
3.2.
Menu navigation
The operation of the device as well as the configuration is done via a push-rotate
button which allows a precise menu navigation and accurate setting of any value.
The encoder can be operated either with a screwdriver or with the delivered knob
which fits in into the screwdriver fitting.