Safety Relay
C6701
DIN EN / IEC 60947-5-1
Operating Instructions
Order No.: 2CDC 113 024 M9701
English
2
The safety switching device must be installed in switchgear cubicles
complying with degree of protection IP32, IP43 or IP54, depending on the
prevailing environmental conditions.
The products described herein are designed to be components of a customized
machinery safety-oriented control system. A complete safety-oriented system
may include safety sensors, evaluators, actuators and signaling components. It
is the responsibility of each company to conduct its own evalution of the effec-
tiveness of the safety system by trained individuals. ABB AG, its subsidiaries
and affiliates (collectively "ABB") are not in a position to evaluate all of the cha-
racteristics of a given system or product or machine not designed by ABB.
ABB accepts no liability for any recommendation that may be implied or stated
herein. The warranty contained in the contract of sale by ABB is the sole war-
ranty of ABB. Any statements contained herein do not create new warranties or
modify existing ones.
The C6701 safety relay can be used in EMERGENCY STOP devices according to
DIN EN / IEC 60947-5-5 and in safety circuits according to
DIN EN / IEC 60204-1, e.g. in movable guards and protective doors or in non-con-
tact protective devices in accordance with DIN EN / IEC 61496-1, electrical
equipment for furnaces in accordance with VDE 0116 and automatic firing sys-
tems for gas burners in accordance with DIN EN 298 . Depending on the external
circuit elements, max. Performance Level PL e / Cat. 4 according to
DIN EN ISO 13849-1 or SIL 3 according to DIN EN / IEC 62061 can be achieved.
The user must carry out an evaluation of the overall systems.
The C6701 safety relay has two reliable solid-state outputs. Three LEDs indicate
the operating state and the function.
When the device is put into operation it runs through a self-test to test the
correct functioning of the internal electronics. All internal circuit components
are monitored for faults cyclically during operation.
Connect the EMERGENCY STOP button and/or the position switches or light
arrays to terminals Y11, Y12 and Y21, Y22. Connect the ON button in series with
the NC contacts of the external actuators to the supply voltage L+ (24 V DC) and
to terminal Y34. Connect cascading input 1 either via a safe output or directly to
the supply voltage L+ (24 V DC).
External actuators or loads can be switched via safe outputs 14, 24. It must be
ensured that the actuators or loads and the C6701 electronic safety relay have
the same frame potential. Paralleling outputs 14 and 24 to increase the load
current is not permissible.
If electronic sensors (light-array monitoring, etc.) are used, and in single-channel
operation, Y35 must be connected to L+ (24 V DC). For autostart operation, Y32
must be connected directly to L+ (24 V DC) and Y34 must be connected to it via
NC contacts of the external actuators.
Use a power pack to IEC 60536 safety class III (SELV or PELV)
for power supply!
1
)
Sensor circuits open; Cross-circuit between the sensors; Short-circuit of
sensors to frame
2
)
Only when using circuit variant with "cross-circuit detection"
3
)
Safe outputs disconnected for test purposes; sufficiently slow actuators are
not affected.
For further data and accessories see Catalog.
Read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before
working on this device.
CAUTION
Reliable functioning of the equipment is only ensured with certi-
fied components.
IMPORTANT NOTICE
Application
Functional description and instructions for connection
Terminal
assignments
Operating
voltage
A1
A2
L+
M
Sensors Y11, Y12
Y21, Y22
Y35
Y32
Y34
Channel 1 EMERGENCY STOP or position switch
Channel 2 EMERGENCY STOP or position switch
With / without cross-circuit detection
Autostart changeover switch
ON button, feedback circuit
Input
1
Cascading input
Outputs
14, 24
Safe Solid-state outputs
Cable
lengths
for 2 x 1.5 mm
2
max. 2000 m (total cable length for sensors)
!
Figures
Fig. I:
Fig. II:
Fig. IIIa:
Fig. IIIb:
Fig. IV:
Fig. V:
Fig. VI:
Fig. VII:
Fig. VIII:
Fig. IX:
Fig. X:
Dimension drawings (dimensions in mm)
Installation / Connection
Safety data
Application data
Internal circuit:
¿
power pack,
À
control logic,
Á
Output 1,
Â
Output 2
Protective-door monitoring, two-channel, autostart
EMERGENCY STOP, single-channel, monitored start *
EMERGENCY STOP, two-channel, monitored start
Light-array monitoring, two-channel, autostart
EMERGENCY STOP, two-channel, monitored start and protective-door
monitoring, autostart
Safety mat, two-channel, autostart
Operating states
LEDs
Operation
POWER
RUN
FAULT
PS
EMERGENCY
STOP
ON button
Outputs
ON
not activated activated
on
activated
1
)
not activated off
not activated not activated off
flashes
on startup self-test approx. 7 sec.
Faults
flashes
• Defect in electronics
• Change in terminal assignment
during operation
• Short-circuit to 24V
2)
off
No supply voltage
Technical data
Permissible ambient temperature T
u
Operation / storage
–25 to +60 °C / –40 to +80 °C
Degree of protection to DIN EN / IEC 60529
IP40, IP20 at terminals
Rated insulation voltage
50 V
Rated impulse withstand voltage
500 V
Rated control supply voltage
24 V DC
Rated power
1.3 W
Operating range
0.9 to 1.15 x U
s
Shock resistance (half-sine) as per
DIN EN / IEC 60068
8
g
/ 10 ms
Weight
150 g
Recovery time after EMERGENCY STOP
min. 200 ms
Recovery time after power failure
7 s
Release time after EMERGENCY STOP
30 ms
Pickup time
max. 40 ms
Short-circuit protection
no fusing necessary!
Dark time
3
)
<
1 ms
Start signal Y34
pulse (min.200 ms / max. 5 s)
Utilization category
as per DIN EN / IEC 60947-5-1
Rated operational
voltage
Rated operational current
per output
DC-13
24 V
1.5 A
Note! This product is obsolete. For replacement see Sentry safety relays.