38
Symptom
Possible Cause
Action
Does not power up
a) Internal fuse (if fitted) is blown
a) Check wiring, rectify fault and replace fuse
b) Internal power switch (if fitted) is OFF
b) Turn power switch ON
c) Power supply connections are incorrect
c) Check connections
Chart does not appear to move
a) Very slow chart speed selected
a) Select required chart speed in
Set Up
Chart Page
b) Chart stop function enabled
b) De-activate source being used to stop
chart – see
Set Up Chart
Page
Pens in recording position but do not drop
Chart stop function enabled
De-activate source used to stop chart – see
onto paper
Set Up Chart
Page
Red pen does not move beyond 94%
When real time event pen is fitted the red pen
Use chart range which prevents the need to go
position on chart
cannot go beyond 94% to prevent pens
beyond 94% of maximum on chart
clashing
Pen lift switch on front panel does not
Pen lift switch is disabled
Enable pen-lift switch in
Set Up Chart
Page
work
Pens do not remain lifted when pen lift key
Auto pen drop feature is enabled
Disable auto pen drop in
Set Up Chart
Page
if
is used
this is not required
Analog inputs are slow to respond
A large filter time has is set
Set digital filter value to give required response
in
Set Up Inputs
Time or date incorrect
Not set for correct local time
Set correct time and date in
Set Up Clock
Page
– refer to
Advanced Software Manual
Totalizers cannot be set to STOP or GO
Operator STOP/GO selection is not enabled
Enable counter STOP/GO in the
Set Up
in the
OPERATOR LEVEL
Totals
Page
Totalizer cannot be set to STOP
Digital signal assigned to the total STOP/GO
De-activate digital signal assigned to total
function is active
STOP/GO function
External relays connected to relays in
Arc suppression capacitors are provided
Remove the arc suppression components –
instrument fail to de-energize
across the relay contacts and capacitor
IC4 and IC5 on mainboard
leakage current may be sufficient to prevent
IC6 and IC7 on standard I/O and analog relay
an external relay from de-energizing
IC3 to IC10 on 4 relay module
Pens return to a different position after a
Pens are interfering with one another due to
Each pen requires the force of 1 gram to lift it
pen-lift or power down
incorrect setting of pens
off the paper. Carefully bend arm (up or down)
close to the plastic moulding to give correct
setting
7
SIMPLE FAULT FINDING