AquaMaster 3 
Electromagnetic flowmeter 

 

MODBUS Tables Supplement COI/FET2XX/MOD/TBL-EN 

 20 

 

MODBUS Protocol 

 

Address

 

AquaMaster 3 
Parameter

 

Name

 

Size 
(bytes)

 

Range/Units

 

MID 

?

 

Note

 

8041

 

190

 

PressureBody

 

1

 

0 to 23

 

 

See Table A.1 — Materials 

8042

 

191

 

PressureWettedParts

 

1

 

0 to 23

 

 

See Table A.1 — Materials 

8043

 

192

 

PressureSeals

 

1

 

0 to 23

 

 

See Table A.1 — Materials 

8044

 

213

 

ABB Reserved

 

1

 

 

y

 

 

8045

 

233

 

TestMode

 

1

 

0 to 1

 

y

 

0 = Off, 1 = On  
(velocity = 1ms

—1

)

 

8046

 

242

 

ClockAdjust

 

2

 

—500 to +500

 

 

Secs/31days

 

8047

 

244

 

ABB Reserved

 

2

 

 

 

 

8048

 

255

 

PressureHeightOffset

 

2

 

±32000 mm

 

 

 

8049

 

289

 

ABB Reserved

 

1

 

 

 

 

8050

 

315

 

SoftwareReset

 

1

 

0 to 1

 

y

 

1 = Reset

 

8051

 

316

 

ABB Reserved

 

1

 

 

 

 

8052

 

317

 

FlowCutOffHigh

 

1

 

0 to 255 mms

—1

 

y

 

Factory flow cut off  
(mains mode)

 

8053

 

320

 

ExtPowerOkThresholdV

 

2

 

5 to 15 V

 

 

 

8054

 

326

 

ABB Reserved

 

1

 

 

 

 

8055

 

327

 

ABB Reserved

 

1

 

 

y

 

 

8056

 

334

 

SoftwareResetCount

 

2

 

 

 

 

8057

 

335

 

WatchdogResetCount

 

2

 

 

 

 

8058

 

336

 

SensorCalTxVersion

 

1

 

 

y

 

 

8059

 

339

 

ABB Reserved

 

2

 

 

 

 

8060

 

342

 

LastTxSoftwareVer

 

1

 

 

y

 

 

8061

 

344

 

ElectrodeVoltsTripBatt

 

1

 

0 to 199 Vx100

 

y

 

 

8062

 

347

 

ABB Reserved

 

1

 

 

 

 

8063

 

352

 

ABB Reserved

 

2

 

 

 

 

8064

 

353

 

ABB Reserved

 

1

 

 

 

 

8065

 

354

 

ABB Reserved

 

1

 

 

 

 

8066

 

358

 

ABB Reserved

 

1

 

 

 

 

8067

 

361

 

ABB Reserved

 

1

 

 

 

 

8068

 

367

 

ABB Reserved

 

1

 

 

 

 

8069

 

379

 

ExtPowerLowThresholdV

 

2

 

5 to 15 V

 

 

 

8070

 

380

 

IntPowerLowThresholdV

 

1

 

31 to 37 Vx10

 

 

 

8071

 

385

 

ABB Reserved

 

1

 

 

 

 

8072

 

386

 

ABB Reserved

 

1

 

 

 

 

8073

 

388

 

ABB Reserved

 

1

 

 

 

 

8074

 

389

 

ABB Reserved

 

1

 

 

 

 

8075

 

394

 

ABB Reserved

 

1

 

 

 

 

8076

 

395

 

ABB Reserved

 

1

 

 

 

 

8077

 

399

 

ABB Reserved

 

1

 

 

 

 

8078

 

400

 

ABB Reserved

 

1

 

 

 

 

8079

 

401

 

ABB Reserved

 

1

 

 

 

 

8080

 

402

 

ABB Reserved

 

1

 

 

 

 

8081

 

405

 

TotaliserLoggingTime

 

1

 

0 to 23 h

 

 

See Note 1

 

8082

 

406

 

ABB Reserved

 

1

 

 

 

 

8083

 

410

 

WindClockSecs

 

2

 

+/— 32400 s

 

 

Adjust clock

 

1

 Refer to AquaMaster 3 Programming Guide COI/FET2XX—EN for settings. 

 

Summary of Contents for AquaMaster 3

Page 1: ...ation information and MODBUS Protocol Register Allocation tables and is applicable to product firmware version WAJC2103 v01 00 00 or above Detailed specifications and recommendations for using and imp...

Page 2: ...committed to teamwork high quality manufacturing advanced technology and unrivalled service and support The quality accuracy and performance of the Company s products result from over 100 years experi...

Page 3: ...ister Usage 4 1 3 1 RW 1 Bit 4 1 3 2 RO 1 Bit 5 1 3 3 RO 8 16 Bit 5 1 3 4 RO String 6 1 3 5 RO 32 Bit 7 1 3 6 RO Float 8 1 3 7 RW 8 16 Bit 8 1 3 8 RW String 10 1 3 9 RW 32 Bit 12 1 3 10 RW Float 13 Ap...

Page 4: ...dered when implementing a MODBUS master to communicate with AquaMaster 3 Transmission mode Remote Terminal Unit RTU slave Response time out 1s Turnaround delay 800ms Interface power up considerations...

Page 5: ...for each Register Address Range and Appendix A provides the Register allocation tables Register Address Range Applicable Function Codes AquaMaster Data Type Description 0001 0500 01 Read Coils 05 Writ...

Page 6: ...le bit types Read Coils 1 to 14 Read all RW 1 Bit items Request Message Hex Response Message Hex Error Message Hex Address 01 Address 01 Function 81 Function 01 Function 01 Exception Code Exception Co...

Page 7: ...Variable Meaning 0 501 0 007 Flow sensor is not reverse wired 1 502 1 008 Flow sensor is a Probe 2 503 1 416 MID read only switch is Active 3 to 7 Not Used 1 3 3 RO 8 16 Bit Read only access to 8 and...

Page 8: ...Each AquaMaster 3 String type requires 18 MODBUS Registers 36 bytes Consequently RO String Register addresses are assigned at intervals of 18 and the Request Message must provide Quantity of Inputs i...

Page 9: ...ters 4 bytes Consequently RO 32 Bit Register addresses are assigned at intervals of 2 and the Request Message must provide Quantity of Inputs in multiples of 2 32 Bit quantities are arranged in big en...

Page 10: ...g Address Hi 13 Byte count 04 Starting Address Lo a8 H Register Value Hi 41 Quantity of Inputs Hi 00 H Register Value Lo 20 Quantity of Inputs Lo 02 L Register Value Hi 00 CRC f4 L Register Value Lo 0...

Page 11: ...Value Hi 00 Register Value Hi 00 Register Value Lo 0e 14 Register Value Lo 0e 14 CRC ae CRC ae CRC 0b CRC 0b Write Multiple Registers 8019 var125 Trip point for high flow 15 Request Message Hex Respo...

Page 12: ...nse Message Hex char Error Message Hex Address 01 Address 01 Function 83 Function 03 Function 03 Exception Code Exception Code Starting Address Hi 27 Byte count 24 Starting Address Lo e8 byte0 41 A Qu...

Page 13: ...Address Lo d6 Starting Address Lo d6 Quantity of Registers Hi 00 Quantity of Registers Hi 00 Quantity of Registers Lo 12 Quantity of Registers Lo 12 Byte count 24 CRC ab byte0 46 F CRC 48 byte1 6c l...

Page 14: ...antity of Registers in multiples of 2 32 Bit quantities are arranged in big endian order Read Holding Registers 12003 to 12004 var224 Totaliser Forward Request Message Hex Response Message Hex Error M...

Page 15: ...s Hi 00 Register Value H Lo 66 Quantity of Inputs Lo 02 Register Value L Hi 66 CRC 0a Register Value L Lo 67 0 9000000 CRC 8c CRC 7c CRC 72 Each AquaMaster 3 RW Float type requires 2 MODBUS Registers...

Page 16: ...al on AquaMaster 3 LCD display 2 053 DisplayReverseTotal 0 Off 1 On 3 054 DisplayNetTotal 0 Off 1 On 4 055 DisplayTariffA 0 Off 1 On 5 056 DisplayTariffB 0 Off 1 On 6 059 DisplayFlowRate 0 Off 1 On 7...

Page 17: ...Sensor settling time mains power 1008 034 ABB Reserved 2 1009 035 ABB Reserved 2 1010 036 ABB Reserved 1 1011 106 CalibrationType 1 0 to 4 See Table A 2 Calibration Types 1012 148 ABB Reserved 1 1013...

Page 18: ...2109 199 TransmitterType 25 AquaMaster 3 2127 200 Manufacturer 25 2145 201 Address1 25 2163 202 Address2 25 2181 203 Address3 25 2199 204 Address4 25 2217 210 CalibrationDate 11 Transmitter calibrati...

Page 19: ...03 002 FlowSensorSoftwareRev 4 4005 003 FlowSensorHardwareRev 4 4007 172 PressureSoftwareRev 4 4009 173 PressureHardwareRev 4 4011 205 HardwareRevisionLevel 4 4013 207 TransmitterUniqueID 4 Transmitte...

Page 20: ...tedBore 4 mm 5035 238 ISpan 4 Factory coil current span factor 5037 239 IZero 4 Factory coil current zero correction 5039 243 CoilCurrent 4 A 5041 258 PulseOutput 4 Hz 5043 294 SignalCalHighCurrent 4...

Page 21: ...to 19 See Note 1 8016 117 FlowCutOffLow 1 0 to 255 mms 1 y Factory flow cut off battery mode 8017 118 UserFlowCutOff 1 0 to 255 y User s flow cut off setting 8018 119 PressureUnits 1 0 to 7 See Note...

Page 22: ...15 V 8054 326 ABB Reserved 1 8055 327 ABB Reserved 1 y 8056 334 SoftwareResetCount 2 8057 335 WatchdogResetCount 2 8058 336 SensorCalTxVersion 1 y 8059 339 ABB Reserved 2 8060 342 LastTxSoftwareVer 1...

Page 23: ...g 25 10271 186 Pressure1stFactory 11 See Table A 4 Date Format 10289 187 PressureLastFactory 11 See Table A 4 Date Format 10307 188 PressureCertNo 25 10325 189 PressureContractNo 25 10343 196 Pressure...

Page 24: ...itted unless MID active 12005 225 TotaliserRev 4 Totaliser units y Write value of 0 permitted unless MID active 12007 226 TotaliserNet 4 Totaliser units y Write value of 0 permitted unless MID active...

Page 25: ...15 110 CustomVelocityUnits 4 per ms 1 13017 113 CustomFlowUnits 4 per m3 s 1 13019 115 FlowUpperRange 4 Flow units y 13021 116 FlowLowerRange 4 Flow units y 13023 120 CustomPressureUnits 4 per mmHg 13...

Page 26: ...ttings 0 Special 1 N A 2 PFA 3 PTFE 4 FEP 5 ABR 6 Rubber WRC 7 Polyurethane 8 HT Rubber 9 Polypropylene 10 PES 11 P E 12 PPS 13 Viton 14 St St 15 C St 16 Brass 17 Gold 18 Titanium 19 Hast B 20 Hast C...

Page 27: ...OW 2 Battery Power FAIL 3 Mains Power ON 4 Mains Power OFF 5 Renewable Power OK 6 Renewable Power LOW 7 Renewable Power OFF Table A 3 External Power Status Modbus register 8030 AquaMaster 3 parameter...

Page 28: ...AquaMaster 3 Electromagnetic flowmeter MODBUS Tables Supplement COI FET2XX MOD TBL EN 26 MODBUS Protocol Notes...

Page 29: ...AquaMaster 3 Electromagnetic flowmeter MODBUS Tables Supplement COI FET2XX MOD TBL EN 27 MODBUS Protocol...

Page 30: ...AquaMaster 3 Electromagnetic flowmeter MODBUS Tables Supplement COI FET2XX MOD TBL EN 28 MODBUS Protocol...

Page 31: ...nalytics Instrumentation pH Conductivity and Dissolved Oxygen Transmitters and Sensors Ammonia Nitrate Phosphate Silica Sodium Chloride Fluoride Dissolved Oxygen and Hydrazine Analyzers Zirconia Oxyge...

Page 32: ...t without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in thi...

Reviews: