background image

Page 7

4.4  Primary Circuit Test

The primary circuit of the breaker has been
tested prior to shipment. Retesting prior to
energization will insure no internal
transportation damages have occurred.
Verification of vacuum can be performed by
a low-frequency AC withstand test.
Additional a contact resistance testl by
performing a contact resistance test is
recommended.

Rated Max

Voltage

Dielectric Test

Value, 1 Minute

Dry AC rms

New Condition

reference

c37.06

Dielectric Test

Value, 1 Minute

Dry AC rms

Field Condition

reference

c37.20.2

4.76kV

19kV

15kV

8.25kV

36kV

27kV

15kV

36kV

27kV

27kV

60kV

45kV

Figure 4.15 Primary low-frequency withstand test
voltages

To verify the integrity of the vacuum
interrupters perform the following low-
frequency withstand voltage test:

1.  Open the breaker (no control power
supplied to breaker)

a. Connect the high potential lead to

one terminal.

b. Ground the remaining 5 terminals

and breaker frame.

2.  Start machine with output potential at 0
(zero) VAC

3.  Increase the potential to the required
voltage (

Figure 4.15

)

4.  Hold for one minute

5.  Decrease potential to 0 (zero) and turn
off machine

6.  Repeat for the remaining 5 terminals

A successful withstand indicates
satisfactory vacuum integrity. Remove
power from the breaker.

Contact resistance is measure at the factory
according to the ANSI 37.09 using a 200A
µohm meter. This DC resistance test should
be performed after each fault the primary
circuit, from terminal to terminal of each
pole unit, in the close position shall be
measured with at least 100 A of dc current

owing in the circuit and shall not exceed

the limit set for the rating of the circuit
breaker by the manufacturer.

Remove lifting angles from breaker.

Note: Breaker will not fully rack in with lifting
angles installed.

 CAUTION

High voltage applied across
an open gap in a vacuum can
produce X-radiation. When
the breaker is fully open the
contact spacing is such that
when tested with the voltages
specified, X-radiation at one
meter is below the level of
concern. A danger could
exist at voltages above the
dielectric test voltage or
reduced contact spacing
caused by a major internal
mechanical failure of the
breaker.

Courtesy of NationalSwitchgear.com

Summary of Contents for AMVAC

Page 1: ...AMVACTM and ADVACTM Breaker commissioning procedures Courtesy of NationalSwitchgear com...

Page 2: ...1VAL0501 MB Rev A Oct 2015 Courtesy of NationalSwitchgear com...

Page 3: ...4 6 Racking DISCONNECT to TEST 10 4 7 In Cell Testing 11 4 8 Racking TEST to CONNECT 11 4 9 Racking CONNECT to TEST 12 4 10 Racking TEST to DISCONNECT 12 4 11 Removal 12 4 12 Standard Color 13 4 13 G...

Page 4: ...egarding the potential hazards for themselves and other personnel in the area These instructions are intended for use by fully qualified personnel and are not a substitute for adequate training experi...

Page 5: ...gh center of gravity into account Carry out loading operations only when it has been ensured that all precautionary measures to protect personnel and materials have been taken into consideration 3 3 S...

Page 6: ...2 Truck mounting WARNING Always follow safe work practices when lifting the circuit breakers to protect the safety of personnel and equipment Always inspect lifting hook for signs of wear or damage be...

Page 7: ...the lift truck facing toward the truck Figure 4 12 It may be necessary to use the racking handle to rotate the racking screw slightly left or right to free up the truck handles Figure 4 8 Lifting hook...

Page 8: ...eaker interlock tabs must engage the slots in the lift truck platform before releasing the foot brake and moving the lift truck Lower the lift truck platform before transporting draw out modules from...

Page 9: ...insure closed indicator is shown c Perform a manual open operation ADVAC only Note if there are any deficiencies during the operations Check the breaker s secondary power requirements listed on the f...

Page 10: ...tential to the required voltage Figure 4 15 4 Hold for one minute 5 Decrease potential to 0 zero and turn off machine 6 Repeat for the remaining 5 terminals A successful withstand indicates satisfacto...

Page 11: ...breaker They are a safe distance from the stationary part of the device located on the housings 2 The TEST position disengages the main disconnecting devices and engages the control contacts This posi...

Page 12: ...ruck foot pedals or lowering the platform with the lift truck control valve Figure 4 19 to lock the locking tabs in the lift truck holding slot The truck platform should be horizontal and aligned with...

Page 13: ...from the DISCONNECTED position to the TEST Position Press down on the racking release handle on the breaker compartment door Figure 4 22 Figure 4 22 Racking release handle 1 Engage the racking screw o...

Page 14: ...ther or both the manual opening switch on the gear or associated breaker relay Check that the breaker is open and appropriate indicating lights are active Figure 4 24 Circuit breaker in CONNECTED posi...

Page 15: ...must disable the UV prior to discharging the breaker 3 Align the locking tabs of the lift truck with the lift truck holding slots in the front of the frame Push the lift truck to the frame to engage...

Page 16: ...galvanized steel Galvanized steel greatly exceeds the paint qualifications of ANSI C37 20 2 Section 5 2 8 4 14 Primary Disconnect Assemblies Circuit breaker primary disconnects consist primarily of a...

Page 17: ...ry air vacuum or if necessary with an OSHA approved solvent 4 Check the calibration of protective relays 5 Follow the recommendations of any individual device instructions furnished for maintenance of...

Page 18: ...or various raw materials The duty of ABB is to facilitate subsequent recycling or disposal at the end of product life During disposal of the product it is always necessary to act in accordance with lo...

Page 19: ...nclusive or covering all contingencies No warranties expressed or implied including warranties of fitness for a particular purpose or merchantability or warranties of fitness for a particular purpose...

Page 20: ...f needed Shutter rollers are clean straight and undamaged Truck wheels are parallel with truck sides and rotate freely Wire harness not loose or damaged Components not loose or missing Mechanism is gr...

Page 21: ...t breaker operates in Connect position Open Close Indicating lights operate as expected Open Close On some ABB Switchgear the Breaker Open indicating light serves as both the breaker is open and that...

Page 22: ...Page 19 Courtesy of NationalSwitchgear com...

Page 23: ...is for general information purposes only While ABB strives to keep the information up to date and correct it makes no representations or warranties of any kind express or implied about the completene...

Reviews: