10 ADVAC AMVAC Commissioning Checklist 1of 2
Breaker Information
Company
Date
Rating
Order #
Serial #
Cat #
Receiving Inspection
Storage & Shipping, was breaker properly stored and shipped in accordance with ABB policy
Shipping crate is undamaged - remove crate
Breaker is still secured to pallet - unsecure breaker
Breaker is clean and free of moisture, corrosion and other environmental intrusions
Breaker is undamaged - take photos, note condition in notes section
Breaker rating label matches order, I.E. ratings, expected accessories - Is the order correct?
Breaker indicating flags and push buttons are correct color and labeling - “OPEN” green, “CLOSE” red
Poles have no cracks or large chips
Primary heat sinks coating is unchipped (no bare metal) - if equipped (2000A & 3000A models)
Primary contacts “tulips” are symmetric and complete - straighten by hand
Primary contacts “tulips” greased at contact points - apply if needed
Primary contacts arms are straight and show no obvious miss alignment
Secondary plugs are undamaged and pins are fully seated and visibly straight
Secondary locking tab is straight and undamaged
Truck ground contact is greased - apply if needed
Shutter rollers are clean, straight and undamaged
Truck wheels are parallel with truck sides and rotate freely
Wire harness - not loose or damaged
Components - not loose or missing
Mechanism is greased where required
Functional Test
Breaker interlock release/truck handles operate freely – insure racking pin has dropped into place
Racking screw release lever moves freely – make sure screw is not rotated and binding on pin
Truck wheels are parallel with truck sides and rotate freely
Breaker manually charges – ADVAC only
Breaker manually closes and opens – ADVAC only
Circuit breaker powers up and goes to “Ready” or “Charged” state in less than 8 seconds
Breaker closes and opens locally – use pushbuttons
Breaker closes and opens remotely – use test cabinet or switchgear
Breaker manually opens – AMVAC only, Close breaker remove power use T-Handle if ordered
Breaker indicators change state appropriately - “OPEN”, “CLOSE”, “Charged” or “Ready”
Operational counter operates – record number of operations ________________
Cell Inspection
Modules interlock slots – unbent and rectangular
Ground bar – visually straight and properly mounted
Interface blocking plate – installed with appropriate rating keyed position facing up
Secondary disconnects – locked into place and slides freely when unlocked
Wheel rails – clean and undamaged