![ABB ACSM1 Series Manual Download Page 50](http://html.mh-extra.com/html/abb/acsm1-series/acsm1-series_manual_2326050.webp)
Drive control and features
50
Speed control features
Jogging
Jogging is typically used during servicing or commissioning to control the machinery
locally. It involves rotating the motor in small increments until the desired load
position is achieved.
Two jogging functions (1 or 2) are available. When a jogging function is activated,
the drive starts and accelerates to the defined jogging speed (parameters
and
) along the defined jogging
acceleration ramp. When the function is deactivated, the drive decelerates to a stop
along the defined jogging deceleration ramp. One push button can be used to start
and stop the drive during jogging.
Jogging functions 1 and 2 are activated by a parameter or through fieldbus. The
source of the jogging command is selected by bit pointer parameters
. For activation through fieldbus, see
The figure and table below describe the operation of the drive during jogging. (Note
that they cannot be directly applied to jogging commands through fieldbus as those
require no enable signal; see parameter
.) They also represent
how the drive shifts to normal operation (= jogging inactive) when the drive start
command is switched on. Jog cmd = State of the jogging input; Jog enable = Jogging
enabled by the source set by parameter
; Start cmd = State of
the drive start command.
Phase Jog
cmd
Jog
enable
Start
cmd
Description
1-2
1
1
0
Drive accelerates to the jogging speed along the acceleration ramp of the jogging function.
2-3
1
1
0
Drive runs at the jogging speed.
3-4
0
1
0
Drive decelerates to zero speed along the deceleration ramp of the jogging function.
4-5
0
1
0
Drive is stopped.
5-6
1
1
0
Drive accelerates to the jogging speed along the acceleration ramp of the jogging function.
6-7
1
1
0
Drive runs at the jogging speed.
7-8
x
0
1
Jog enable is not active; normal operation continues.
8-9
x
0
1
Normal operation overrides the jogging. Drive follows the speed reference.
9-10
x
0
0
Drive decelerates to zero speed along the active deceleration ramp.
10-11
x
0
0
Drive is stopped.
Time
Speed
1
2
3
4
5
6
7
8
9
10 11
12 13 14 15 16
Jogging example
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...