Parameters and firmware blocks
95
2.12
FBA MAIN CW
(page
)
Control Word for fieldbus communication.
Log. = Logical combination (ie, Bit AND/OR Selection parameter). Par. = Selection parameter. See
on page
429.
Bit
Name
Val.
Information
Log.
Par.
0
STOP*
1
Stop according to the stop mode selected by
STOP MODE or according to the requested stop
mode (bits 2…6).
Note:
Simultaneous STOP and
START commands result in a stop command.
OR
0
No operation
1
START
1
Start.
Note:
Simultaneous STOP and START
commands result in a stop command.
OR
0
No operation
2
STPMODE
EM OFF*
1
Emergency OFF2 (bit 0 must be 1): Drive is
stopped by cutting off the motor power supply (the
inverter IGBTs are blocked). The motor coasts to
stop. The drive will restart only with the next rising
edge of the start signal when the run enable signal
is on.
AND
-
0
No operation
3
STPMODE
EM STOP*
1
Emergency stop OFF3 (bit 0 must be 1): Stop within
the time defined by
AND
0
No operation
4
STPMODE
OFF1*
1
Emergency stop OFF1 (bit 0 must be 1): Stop along
the currently active deceleration ramp.
AND
0
No operation
5
STPMODE
RAMP*
1
Stop along the currently active deceleration ramp.
-
0
No operation
6
STPMODE
COAST*
1
Coast to stop.
-
0
No operation
7
RUN
ENABLE
1
Activate run enable.
AND
0
Activate run disable.
8
RESET
0->1 Fault reset if an active fault exists.
OR
other No operation
9
JOGGING 1
1
Activate jogging function 1. See section
on
page
OR
0
Jogging function 1 disabled
* If all stop mode bits 2…6 are 0, stop mode is selected by
. Coast stop (bit 6)
overrides the emergency stop (bit 2/3/4). Emergency stop overrides the normal ramp stop (bit 5).
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...