Parameters and firmware blocks
124
Bit pointer: Group, index and bit
10.11
EM STOP OFF1
(see above)
Selects the source for the emergency stop OFF1. 0 = OFF1 active: The drive is stopped with the
active deceleration time.
Emergency stop can also be activated through fieldbus (
See section
on page
Note:
This parameter cannot be changed while the drive is running.
Bit pointer: Group, index and bit
10.12
START INHIBIT
(see above)
Enables the start inhibit function. The start inhibit function prevents drive restart (ie, protects against
unexpected start) if
• drive trips on a fault and fault is reset.
• run enable signal activates while the start command is active. See parameter
• control changes from local to remote.
• external control switches from EXT1 to EXT2 or from EXT2 to EXT1.
An active start inhibit can be reset with a stop command.
Note that in certain applications it is necessary to allow the drive to restart.
(0)
Disabled
Start inhibit function disabled.
(1)
Enabled
Start inhibit function enabled.
10.13
FB CW USED
(see above)
Selects the source for the control word when fieldbus (FBA) is selected as the external start and stop
control location (see parameters
default, the source is parameter
.
Note:
This parameter cannot be changed while the drive is running.
Value pointer: Group and index
10.14
JOG2 START
(see above)
If enabled by parameter
, selects the source for the activation of jogging function
2. 1 = Active. (Jogging function 2 can also be activated through fieldbus regardless of parameter
.)
Note:
This parameter cannot be changed while the drive is running.
Bit pointer: Group, index and bit
10.15
JOG ENABLE
(see above)
Selects the source for enabling parameters
.
Note:
Jogging can be enabled using this parameter only when no start command from an external
control location is active. On the other hand, if jogging is already enabled, the drive cannot be started
from an external control location apart from jog commands through fieldbus.
Bit pointer: Group, index and bit
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...