Parameters and firmware blocks
208
50.12
FBA CYCLE TIME
(see above)
Selects the fieldbus communication speed. The default selection is
. Lowering the speed
reduces the CPU load.
The table below shows the read/write intervals for cyclic and cyclic low data with each parameter
setting.
*Cyclic data consists of fieldbus CW and SW, Ref1 and Ref2, and Act1 and Act2.
**Cyclic low data consists of the parameter data mapped to parameter groups
(0)
Slow
Slow speed selected.
(1)
Normal
Normal speed selected.
(2)
Fast
Fast speed selected.
50.20
FB MAIN SW FUNC
(see above)
Contains various compatibility settings especially for drive retrofits.
Selection
Cyclic*
Cyclic low*
Slow
10 ms
10 ms
Normal
2 ms
10 ms
Fast
500 us
2 ms
Bit
Name
Information
0
Run enable func 1 = Parameter only:
Bit 1 of
is set to 1 whenever the external run
enable signal (par.
) is 1.
0 = Param AND Fb cw:
Bit 1 of
is set to 1 whenever both the external
run enable signal (par.
) is 1 AND
bit 7 (RUN ENABLE) are 1.
1
Mech brake func 1 = Force ramp stop:
Drive always uses ramp stop when a mechanical brake is used.
0 = Allow coast stop:
Coast stop is allowed when a mechanical brake is used.
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...