40.07
IR COMPENSATION
(see above)
Defines the relative output voltage boost at zero speed (IR compensation). The function is useful in
applications with high break-away torque when no DTC motor can be applied.
This parameter is only effective when parameter
is set to
.
0…50%
IR compensation.
40.10
FLUX BRAKING
(see above)
Defines the level of braking power.
(0)
Disabled
Flux braking is disabled.
(1)
Moderate
Flux level is limited during the braking. Deceleration time is longer
compared to full braking.
(2)
Full
Maximum braking power. Almost all available current is used to
convert the mechanical braking energy to thermal energy in the motor.
U
/
U
N
(%)
f
(Hz)
Field weakening point
Relative output voltage. No IR
compensation.
Relative output voltage. IR
compensation set to 15%.
15%
100%