![ABB ACSM1-04 Series Hardware Manual Download Page 75](http://html.mh-extra.com/html/abb/acsm1-04-series/acsm1-04-series_hardware-manual_2656075.webp)
Technical data
75
AC input (supply) connection
Voltage (
U
1
)
380 … 480 V AC +10%/-15%, 3-phase
Frequency
50 … 60 Hz ±5%
Network type
Grounded (TN, TT) or ungrounded (IT).
Note:
Connection to an ungrounded (IT) or corner-grounded delta network is not allowed
at altitudes of 2000 m (6600 ft) or higher.
Imbalance
Max.
±3% of nominal phase to phase input voltage
Fundamental power factor
(cos phi
1
)
0.98 (at nominal load)
Terminals
With cable sizes from 16 to 70 mm
2
(AWG6 to AWG2/0): Posts for crimp lugs (lugs not
included).
With cable sizes from 95 to 185 mm
2
(AWG3/0 to AWG400): Screw lugs (included).
Grounding clamps.
Motor connection
Motor types
Asynchronous induction motors, asynchronous servo motors, synchronous permanent
magnet motors, permanent magnet servo motors
Frequency
0 … 500 Hz
Current
See section
Switching frequency
Selectable between 1…8 kHz. Default: 4 kHz, above which output current derated
Maximum motor cable
length
50 m (164 ft) with screened cable
75 m (246 ft) with unscreened cable
Terminals
With cable sizes from 16 to 70 mm
2
(AWG6 to AWG2/0): Posts for crimp lugs (lugs not
included).
With cable sizes from 95 to 185 mm
2
(AWG3/0 to 400): Screw lugs (included).
Grounding clamps.
JCU Control Unit
Power supply
24 V (±10%) DC, 1.6 A
Supplied from the power unit of the drive, or from external power supply through connector
X1 (pitch 3.5 mm, wire size 1.5 mm
2
).
Relay output (X2)
Connector pitch 5 mm, wire size 2.5 mm
2
250 V AC / 30 V DC, 2 A
Protected by varistors
Digital inputs DI1…DI6 (X3)
Connector pitch 3.5 mm, wire size 1.5 mm
2
Logic levels: “0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Filtering: Adjustable, 0.25 ms min. (see also
Firmware Manual)
Summary of Contents for ACSM1-04 Series
Page 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 55 to 110 kW ...
Page 2: ......
Page 4: ......
Page 18: ...About this manual 18 ...
Page 22: ...The ACSM1 04 22 ...
Page 64: ...Electrical installation 64 ...
Page 70: ...Maintenance 70 ...
Page 82: ...Technical data 82 ...
Page 88: ...Dimension drawings 88 Drive module ...
Page 89: ...Dimension drawings 89 Drive module continued from previous page ...
Page 91: ......