![ABB ACSM1-04 Series Hardware Manual Download Page 55](http://html.mh-extra.com/html/abb/acsm1-04-series/acsm1-04-series_hardware-manual_2656055.webp)
Electrical installation
55
Procedure
1. Remove the plastic shroud covering the main terminals. Remove the two screws
at the sides, then release the two clips on the front edge as shown.
2. Connect the twisted shields of the power cables to the grounding terminals of the
drive module.
3. Connect the phase conductors of the supply cable to the U1, V1 and W1
terminals, and the phase conductors of the motor cable to the U2, V2 and W2
terminals. The recommended stripping length is 28 mm (1.1”).
4. Secure the cables mechanically outside the drive module.
5. Cut suitable slots on the edge of the plastic shroud to accommodate the power
cables. Refit the shroud.
6. Ground the other end of the supply cable shield or PE conductor at the
distribution board.