368 Parameters
(Effective in the master only.) Selects how the drive reacts to a
fault in a follower.
See also parameter
.
Note:
Each follower must be configured to transmit its status
word as one of the three data words in parameters
. In the master, the corresponding target
parameter (
) must be set to
.
No action
No action taken. Unaffected drives on the master/follower link
will continue running.
0
Warning
The drive generates a warning (
1
Fault
. All followers will be stopped.
2
Interlocks the starting of the master to the status of the
followers.
See also parameter
.
Note:
Each follower must be configured to transmit its status
word as one of the three data words in parameters
. In the master, the corresponding target
parameter (
) must be set to
.
MSW bit 0
The master can only be started if all followers are ready to
switch on (bit 0 of
in each follower is
on).
0
MSW bit 1
The master can only be started if all followers are ready to
operate (bit 1 of
in each follower is
on).
1
MSW bits 0 + 1
The master can only be started if all followers are ready to
switch on and ready to operate (bits 0 and 1 of
2
Always
The starting of the master is not interlocked to the status of the
followers.
3
MSW bit 12
The master can only be started if user-definable bit 12 of
in each follower is on. See parameter
4
MSW bits 0 + 12
The master can only be started if both bit 0 and bit 12 of
in each follower are on.
5
MSW bits 1 + 12
The master can only be started if both bit 1 and bit 12 of
in each follower are on.
6
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...