344 Parameters
Defines a maximum limit for control panel speed reference in
external control.
In local control, the limits in parameter group
force. See section
Local control vs. external control
(page
).
30000.00
rpm
-30000.00 …
30000.00 rpm
Maximum speed reference.
See par.
Minimum ext
frequency ref panel
Defines a minimum limit for control panel frequency reference
in external control.
In local control, the limits in parameter group
force. See section
Local control vs. external control
(page
).
-500.00 Hz
-500.00 … 500.00
Hz
Minimum frequency reference.
See par.
Maximum ext
frequency ref panel
Defines a maximum limit for control panel frequency reference
in external control.
In local control, the limits in parameter group
force. See section
Local control vs. external control
(page
).
500.00 Hz
-500.00 … 500.00
Hz
Maximum frequency reference.
See par.
Selects an actual value to be displayed in the top right corner
of the control panel. This parameter is only effective when the
control panel is not an active reference source.
Automatic
The active reference is displayed.
0
Process PID
setpoint actual
(see page
).
1
). -
50
Fieldbus communication configuration.
See also chapter
Fieldbus control through a fieldbus adapter
Enables/disables communication between the drive and
fieldbus adapter A, and specifies the slot the adapter is
installed into.
Note:
This parameter cannot be changed while the drive is
running.
Disable
Communication between drive and fieldbus adapter A
disabled.
0
Option slot 1
Communication between drive and fieldbus adapter A
enabled. The adapter is in slot 1.
1
Option slot 2
Communication between drive and fieldbus adapter A
enabled. The adapter is in slot 2.
2
Option slot 3
Communication between drive and fieldbus adapter A
enabled. The adapter is in slot 3.
3
Selects how the drive reacts upon a fieldbus communication
break. A time delay for the action can be defined by parameter
.
No action
No action taken.
0
Fault
. This only occurs if
control is expected from the FBA A interface (FBA A selected
as source of start/stop/reference in the currently active control
location), or if supervision is forced using parameter
1
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...