Parameters 301
Warning only
Drive generates warning
when the
motor is overloaded to the warning level, that is, parameter
reaches value 88.0%.
1
Warning and fault
Drive generates warning
when the
motor is overloaded to the warning level, that is, parameter
reaches value 88.0%.
Drive trips on fault
when the motor is
overloaded to the fault level, that is, parameter
reaches value 100.0%.
2
Defines the motor overload class to be used. The class of
protection is specified by the user as the time for tripping at
7.2 times (IEC 60947-4-1) or 6 times (NEMA ICS) the tripping
level current.
See section
(page
Class 5
Motor overload class 5.
0
Class 10
Motor overload class 10.
1
Class 20
Motor overload class 20.
2
Class 30
Motor overload class 30.
3
Class 40
Motor overload class 40.
4
Shows the calculated temperature of the motor cable. See
section
Thermal protection of motor cable
(page
102% = overtemperature warning (
106% = overtemperature fault (
This parameter is read-only.
0.0%
0.0 … 200.0%
Calculated temperature of motor cable.
1 = 1%
Specifies the continuous current of the motor cable for the
thermal protection function in the control program.
WARNING!
The value entered in this parameter must
be limited according to all factors affecting the
loadability of the cable, such as ambient temperature,
cabling arrangement, and shrouding. Refer to the technical
data from the cable manufacturer.
10000.00 A
0.00 … 10000.00 A Continuous current-carrying capacity of motor cable.
1 = 1 A
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...