Parameters 225
Activates the variable slope function, which controls the slope
of the speed ramp during a speed reference change. This
allows for a constantly variable ramp rate to be generated,
instead of just the standard two ramps normally available.
If the update interval of the signal from an external control
system and the variable slope rate (
are equal, the resulting speed reference (
) is a straight line.
This function is only active in remote control.
Off
Variable slope disabled.
0
On
Variable slope enabled (not available in local control).
1
Source selection (see
). -
Defines the rate of the speed reference change when variable
slope is enabled by parameter
.
For the best result, enter the reference update interval into
this parameter.
50 ms
2…30000 ms
Variable slope rate.
1 = 1 ms
Displays the speed correction term for the load share function
with a speed-controlled follower drive.
See section
Load share function with a speed-controlled
(page
This parameter is read-only.
-
-30000.00 …
30000.00 rpm
Speed correction term.
See par.
Follower speed
correction enable
With a speed-controlled follower, selects the source for
enabling/disabling the load share function.
See section
Load share function with a speed-controlled
(page
0 = Disabled
1 = Enabled
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
No.
Name/Value
Description
Def
/
FbEq16
t
Speed
reference
Speed reference
Time
A
t = update interval of signal from external control system
A = speed reference change during t
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...