208 Parameters
DI6
Digital input DI6 (
, bit 5).
8
DIO1
Digital input/output DIO1 (
, bit 0).
11
DIO2
Digital input/output DIO2 (
, bit 1).
12
). -
Defines the zero speed limit. The motor is stopped along a
speed ramp (when ramped stop is selected) until the defined
zero speed limit is reached. After the zero speed delay, the
motor coasts to a stop.
Note:
If you use a value below the default, make sure the
drive is able to stop.
30.00 rpm
0.00 … 30000.00
rpm
Zero speed limit.
See par.
Defines the delay for the zero speed delay function. The
function is useful in applications where a smooth and quick
restarting is essential. During the delay, the drive knows the
rotor position accurately.
0 ms
Without zero speed delay:
The drive receives a stop command and decelerates along a
ramp. When actual motor speed falls below the value of
parameter
, inverter modulation is
stopped and the motor coasts to a standstill.
With zero speed delay:
The drive receives a stop command and decelerates along a
ramp. When actual motor speed falls below the value of
parameter
, the zero speed delay
function activates. During the delay the function keeps the
speed controller live: the inverter modulates, motor is
magnetized and the drive is ready for a quick restart. Zero
speed delay can be used e.g. with the jogging function.
0 … 30000 ms
Zero speed delay.
1 = 1 ms
No.
Name/Value
Description
Def
/
FbEq16
Speed controller switched off:
Motor coasts to a stop.
Speed
Time
Speed controller remains
active. Motor is decelerated to
true zero speed.
Speed
Time
Delay
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...