Parameters 207
Ramp
Stop along the active deceleration ramp. See parameter
group
.
1
Torque limit
Stop according to torque limits (parameters
and
). 2
Selects the way the motor is stopped when an emergency
stop command is received.
The source of the emergency stop signal is selected by
parameter
.
(
b1);
(
b2)
Ramp stop (Off1)
With the drive running:
• 1 = Normal operation.
• 0 = Normal stop along the standard deceleration ramp
defined for the particular reference type (see section
]). After the drive has stopped,
it can be restarted by removing the emergency stop signal
and switching the start signal from 0 to 1.
With the drive stopped:
• 1 = Starting allowed.
0 = Starting not allowed.
0
Coast stop (Off2)
With the drive running:
• 1 = Normal operation.
• 0 = Stop by coasting. The drive can be restarted by
restoring the start interlock signal and switching the start
signal from 0 to 1.
With the drive stopped:
• 1 = Starting allowed.
• 0 = Starting not allowed.
1
Eme ramp stop
(Off3)
With the drive running:
• 1 = Normal operation.
• 0 = Stop by ramping along emergency stop ramp defined
by parameter
. After the drive
has stopped, it can be restarted by removing the
emergency stop signal and switching the start signal from 0
to 1.
With the drive stopped:
• 1 = Starting allowed.
0 = Starting not allowed.
2
Selects the source of the emergency stop signal. The stop
mode is selected by parameter
.
0 = Emergency stop active
1 = Normal operation
Note:
This parameter cannot be changed while the drive is
running.
;
(
b1,
b2)
Active (false)
0.
0
Inactive (true)
1.
1
DIIL
DIIL input (
, bit 15).
2
DI1
Digital input DI1 (
, bit 0).
3
DI2
Digital input DI2 (
, bit 1).
4
DI3
Digital input DI3 (
, bit 2).
5
DI4
Digital input DI4 (
, bit 3).
6
DI5
Digital input DI5 (
, bit 4).
7
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...