28   Parameter settings

Parameters for the STO function

These parameters are related to the STO function of the FSO module. With stop category 
0, the FSO module activates the STO function in overtemperature situations.

 

In addition, 

the FSO module can activate the STO function in fault situations.

Index

Name

Example 
value

Description

STO.02

STO 
acknowledgement

Automatic
or 
Manual

Sets the acknowledgement method used in the STO, SSE and 
SS1 functions.

Automatic

: The FSO module resets the STO function 

automatically after the STO request have been removed.

Manual

: The FSO module reads the external 

acknowledgement signal through the digital input defined by 
parameter 

FSOGEN.42

. In the safety functions described in 

this guide, you can use this setting to implement a manual 
reset for the motor temperature protection function in the FSO 
module (see section 

Resetting the safety function

 on 

page

19

).

STO.11

STO input A

STO:
DI X113:1 & 
X114:1 
SS1: None

Sets the digital input that is connected to the primary input of 
the STO function.

Note

: The default value after factory reset is 

DI X113:1 & 

X114:1

. Always check this parameter after factory reset.

STO.12

STO input B

None

Sets the digital input that is connected to the secondary input 
of the STO function.

STO.13

Restart delay after 

STO

2000 ms

Sets the time after which the restart of the drive is allowed 
after the FSO module has activated the STO function and 
opened the drive STO circuit. With this parameter, you can 
allow a restart of the drive before the motor has stopped (fly-
start). This parameter is valid only if the STO function is 
requested from STO input A (

STO.11

) or STO input B 

(

STO.12

).

STO function: Adjust the default value when necessary. If you 
do not want to use the fly-start feature, set this parameter to 
the same value as parameter 

STO.14

.

SS1 function: This value has no effect.

STO.14

Time to zero speed 

with STO or modoff

2000 ms

Sets the time after which the acknowledgement is allowed 
after coast stop in the STO and SSE functions

Set this 

parameter value to the estimated time in which the motor 
coasts to a stop from the maximum speed.
STO function: This parameter sets the time after which the 
STO function is completed. Parameter 

STO.13

 defines the 

time after which the restart of the drive is allowed. Adjust the 
value when necessary.
SS1 function: This parameter is used only when the motor 
speed does not follow the ramp settings or the time monitoring 
limit is exceeded and the FSO module activates the STO 
function. Adjust the value when necessary.
When a safety encoder is used: This parameter is relevant 
only if an encoder or FSE module failure occurs. The FSO 
module goes into the Fail-safe mode and activates the STO 
function. For more information, see the FSO-21 module user’s 
manual.

Note

: The default value after factory reset is 

3,600,000 ms

Always check this parameter after factory reset.

SBC usage

SBC.11

STO SBC usage

None

Sets how the mechanical brake is used together with the STO 
function.
In the safety functions described in this guide, this feature is 
not used. Make sure that the value is 

None

.

Summary of Contents for ACS880 Series

Page 1: ...BB industrial drives Application guide ATEX certified Safe disconnection function Ex II 2 GD ACS880 3 3 3 Ex motor Relay 24 240 V AC DC Sensor Potentially explosive atmosphere 3 4 24 V Control circuit...

Page 2: ...AXD50000025169 ACS880 14 and 34 single drive module packages hardware manual 3AXD50000022021 ACS880 104 inverter modules hardware manual 3AUA0000104271 ACS880 104LC inverter modules hardware manual 3A...

Page 3: ...Application guide ATEX certified Safe disconnection function Ex II 2 GD for ACS880 drives option Q971 3AUA0000132231 Rev D EN EFFECTIVE 2018 06 13 2018 ABB Oy All Rights Reserved Table of contents...

Page 4: ......

Page 5: ...of the safety function 15 Connection diagram 16 One channel connection to drive STO terminals 17 General 17 Resetting the safety function 17 Indications of the safety function 17 Connection diagram 18...

Page 6: ...ntrol 31 4 Technical data Contents of this chapter 33 Related standards and directives 33 Safety data 34 Drive inverter module STO function 34 Drive inverter module STO function and an FSO module 34 S...

Page 7: ...ion function option Q971 of the drive Read the guide before working on the drive You must know the fundamentals of electricity wiring electrical components electrical schematic symbols and ATEX Ex reg...

Page 8: ...ing motors equipped with sine filters and made sure by measuring that there is no dangerous voltage present WARNING The STO function of ACS880 drives cannot prevent the intermediate DC current from fl...

Page 9: ...hermal protection make sure that the drive inverter module is equipped with the ATEX certified Safe disconnection function option Q971 motor thermal protection relay is ATEX compliant motor thermal pr...

Page 10: ...afety functions module which does not support the use of safety encoders FSO 21 Safety functions module which supports the FSE 31 module and the use of safety encoders HFT Hardware fault tolerance IEC...

Page 11: ...erent contexts the STO circuit in the drive the drive STO function the STO safety function in the FSO module Safety functions in the FSO module eg STO SSE and SS1 activate the drive STO function that...

Page 12: ...12 Introduction...

Page 13: ...STO connection of the drive In this case the FSO module activates the STO function of the drive that is opens the drive STO circuit either immediately or after a deceleration ramp Note You cannot con...

Page 14: ...21 safety functions module user s manual 3AXD50000015614 English You can also use the FPTC 02 ATEX certified thermistor protection module Ex II 2 GD option L537 Q971 to implement the ATEX compliant m...

Page 15: ...e of the system with Ex ATEX regulations When the protection relay detects motor overtemperature the drive must not restart before a manual reset command You can implement a manual reset in the ATEX c...

Page 16: ...necessary 2 You can use the drive STO function for several external safety functions at the same time for example ATEX compliant motor thermal protection and emergency stop If you do you must connect...

Page 17: ...e safety function A manual reset is mandatory in the temperature protection function if it is required for ensuring the compliance of the system with Ex ATEX regulations When the protection relay dete...

Page 18: ...mal protection and emergency stop If you do you must connect the STO activation switches or relays used in other safety functions in series with the protection relay 3 The STO function of the drive mu...

Page 19: ...equired for ensuring the compliance of the system with Ex ATEX regulations When the protection relay detects motor overtemperature the drive must not restart before a manual reset command You can impl...

Page 20: ...EX compliant protection relay The relay monitors a sensor circuit and de energizes the FSO module input by opening the control circuits when necessary When you install the equipment make sure that you...

Page 21: ...this one channel connection there is no redundant connection between the protection relay and FSO module Still the STO connection signal between the FSO module and STO circuit is redundant When you in...

Page 22: ...rotection relay test to the start up and acceptance test of the motor thermal protection circuit See the relay manual for the relay tests Wiring General wiring instructions Wire only the sensor circui...

Page 23: ...ertificate of the Ex motor typically requires that you set a minimum limit for the switching frequency of the drive For ABB Ex motors use parameter 95 15 to set the required minimum switching frequenc...

Page 24: ...or digital input DI6 you can also use another digital input When off 0 the function triggers the user selected indication and shows the user defined message To configure the motor overtemperature indi...

Page 25: ...of the application minimum and maximum speeds parameter group 30 maximum current power and torque group 30 acceleration and deceleration times stall protection parameters 31 24 31 28 motor load curve...

Page 26: ...FSO module In the second case it activates the SS1 function Example values are given for both cases Always consider which stop category is more appropriate for the motor in overtemperature situations...

Page 27: ...lerated the motor speed below this value Adjust the default value when necessary Note This parameter is used only with FSO 21 and when a safety encoder is used in the application FSOGEN 61 STO indicat...

Page 28: ...h this parameter you can allow a restart of the drive before the motor has stopped fly start This parameter is valid only if the STO function is requested from STO input A STO 11 or STO input B STO 12...

Page 29: ...rgency ramp Sets the type of the SSE function Immediate STO The FSO module activates the drive STO function immediately after the SSE request Emergency ramp The FSO module first ramps down the motor s...

Page 30: ...er 23 23 see section SS1 ramp parameters in the drive inverter module below 200 202 SAR speed scaling 1500 rpm Sets a speed value that the FSO module uses as a reference point in ramp parameter calcul...

Page 31: ...otection circuit pay special attention to the control of the mechanical brake If the motor deceleration by the mechanical brake causes extra heat generation in the ATEX area make sure that the use of...

Page 32: ...32 Parameter settings...

Page 33: ...s required for the safe functioning of equipment with respect to explosion risks IEC 61508 2010 Part 1 General Requirements Part 2 Requirements for electrical electronic programmable electronic safety...

Page 34: ...on FSO module on page 26 in chapter Parameter settings The FSE 31 module is included in the calculations only if a safety encoder is used in the application the FSO 21 module is configured to activate...

Page 35: ...e times The response time of the Safe disconnection STO function is 50 ms for all ACS880 drives For the exact response times for each drive inverter module type see the drive inverter module hardware...

Page 36: ...ares that the product conforms with European ATEX Product Directive 2014 34 EU Notified Body VTT Expert Services Ltd 2 Specific marking of explosion protection 3 II Product for other than mining appli...

Page 37: ...Technical data 37 ATEX certificate...

Page 38: ...38 Technical data...

Page 39: ...Technical data 39...

Page 40: ...40 Technical data Declarations of Conformity Note If the Declaration of Conformity is needed in any other official language of European Union than in English contact ABB...

Page 41: ...Technical data 41 Note If the Declaration of Conformity is needed in any other official language of European Union than in English contact ABB...

Page 42: ...42 Technical data...

Page 43: ...contacts can be found by navigating to www abb com searchchannels Product training For information on ABB product training navigate to new abb com service training Providing feedback on ABB manuals Y...

Page 44: ...www abb com drives www abb com drivespartners 3AUA0000132231 Rev D EN 2018 06 13 Contact us...

Reviews: