Implementing a motor thermal protection circuit 17
One-channel connection to drive STO terminals
General
This section describes an implementation of the ATEX-compliant motor thermal protection
circuit:
•
The circuit uses the ATEX-certified Safe disconnection function (Q971) of the
drive.
•
There is a one-channel (non-redundant) connection of the motor protection relay to
the drive STO terminals. Both STO inputs of the drive are connected to same output
contact of the protection relay.
•
One output contact of the protection relay is connected to a digital input of the drive.
•
The drive shows an overtemperature indication when the digital input switches off (the
protection relay trips).
If you plan to use the one-channel (non-redundant) connection, make sure that you can
reach the necessary safety integrity level (SIL). According to EN 50495, SIL1 is sufficient
for the protection of category 2 and 3 equipment.
Note:
The STO function of the drive must always have a redundant connection. See
on page
Resetting the safety function
A manual reset is mandatory in the temperature protection function, if it is required for
ensuring the compliance of the system with Ex/ATEX regulations. When the protection
relay detects motor overtemperature, the drive must not restart before a manual reset
command. You can implement a manual reset in the ATEX-compliant protection relay
(recommended).
In this example, you can also configure a manual reset in the drive with the motor
overtemperature or STO indication parameters (see section
on page
Indications of the safety function
In this example, you can use the drive STO or the motor overtemperature indication. See
section
Reset method and status indications
on page
If you want to avoid parallel indications in motor overtemperature situations, you can set
one or several of the indication parameters value to
No indication
(or
None
) or
Event
:
•
the motor overtemperature indication with drive parameters
31.01...31.02
or
35.11...35.12
(see page
),
•
the STO indication in the drive with drive parameter
31.22 STO indication run/stop
Note
: Make sure that at least one of these indications generates a fault if the protection
relay does not contain a manual reset.
Summary of Contents for ACS880 Series
Page 4: ......
Page 12: ...12 Introduction...
Page 32: ...32 Parameter settings...
Page 37: ...Technical data 37 ATEX certificate...
Page 38: ...38 Technical data...
Page 39: ...Technical data 39...
Page 42: ...42 Technical data...
Page 44: ...www abb com drives www abb com drivespartners 3AUA0000132231 Rev D EN 2018 06 13 Contact us...