Fault tracing 417
A888
Edge counter 1
(Editable message text)
Programmable warning:
Warning generated by
edge counter 1.
Check the source of the warning
(parameter
A889
Edge counter 2
(Editable message text)
Programmable warning:
Warning generated by
edge counter 2.
Check the source of the warning
(parameter
A88A
Value counter 1
(Editable message text)
Programmable warning:
Warning generated by
value counter 1.
Check the source of the warning
(parameter
A88B
Value counter 2
(Editable message text)
Programmable warning:
Warning generated by
value counter 2.
Check the source of the warning
(parameter
A88C
Device clean
Warning generated by an
on-time timer.
Programmable warnings:
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
0:
1:
10:
.
A88D
DC capacitor
A88E
Cabinet fan
A88F
Cooling fan
A890
Additional cooling
A8A0
AI supervision
Programmable warning:
An analog signal is
outside the limits
specified for the analog
input.
Check signal level at the analog input.
Check the wiring connected to the
input.
Check the minimum and maximum
limits of the input in parameter group
A8B0
Signal supervision
(Editable message text)
Programmable warning:
Warning generated by a
signal supervision
function.
Check the source of the warning
(parameter
or
A8B1
Signal supervision 2
(Editable message text)
Programmable warning:
Warning generated by
the signal supervision 2
function.
Check the source of the warning
(parameter
).
A8B2
Signal supervision 3
(Editable message text)
Programmable warning:
Warning generated by
the signal supervision 3
function.
Check the source of the warning
(parameter
).
A8C0
Fan service counter
A cooling fan has reached
the end of its estimated
lifetime. See parameters
.
Check the auxiliary code. The code
indicates which fan is to be replaced.
0: Main cooling fan
1: Auxiliary cooling fan
2: Auxiliary cooling fan 2
3: Cabinet cooling fan
4: PCB compartment fan
Refer to the hardware manual of the
drive for fan replacement instructions.
Code
(hex)
Warning
Cause
What to do
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...