334 Parameters
(Visible when an absolute encoder is selected)
Selects the maximum encoder calculation time for an
EnDat encoder.
Note: This parameter needs to be set only when an EnDat
encoder is used in continuous mode, ie. without
incremental sin/cos signals (supported only as encoder 1).
See also parameter
.
10 us
10 microseconds.
0
100 us
100 microseconds.
1
1 ms
1 millisecond.
2
50 ms
50 milliseconds.
3
(Visible when an absolute encoder is selected)
Selects the transmission cycle for an SSI encoder.
Note: This parameter needs to be set only when an SSI
encoder is used in continuous mode, ie. without
incremental sin/cos signals (supported only as encoder 1).
See also parameter
.
50 us
50 microseconds.
0
100 us
100 microseconds.
1
200 us
200 microseconds.
2
500 us
500 microseconds.
3
1 ms
1 millisecond.
4
2 ms
2 milliseconds.
5
(Visible when an absolute encoder is selected)
Defines the length of an SSI message. The length is
defined as the number of clock cycles. The number of
cycles can be calculated by adding 1 to the number of bits
in an SSI message frame.
2
2…127
SSI message length.
-
(Visible when an absolute encoder is selected)
With an SSI encoder, defines the location of the MSB
(most significant bit) of the position data within an SSI
message.
1
1…126
Position data MSB location (bit number).
-
(Visible when an absolute encoder is selected)
With an SSI encoder, defines the location of the MSB
(most significant bit) of the revolution count within an SSI
message.
1
1…126
Revolution count MSB location (bit number).
-
(Visible when an absolute encoder is selected)
Selects the data format for an SSI encoder.
Binary
Binary code.
0
Gray
Gray code.
1
(Visible when an absolute encoder is selected)
Selects the baud rate for an SSI encoder.
10 kBit/s
10 kbit/s.
0
50 kBit/s
50 kbit/s.
1
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...