• no danger of overheating is caused to the resistor or nearby materials, and
• the temperature of the room the resistor is located in does not exceed the allowed
maximum.
Supply the resistor with cooling air or coolant according to the resistor manufacturer’s
instructions.
WARNING!
The materials near the brake resistor must be non-flammable. The surface
temperature of the resistor is high. Air flowing from the resistor is of hundreds of
degrees Celsius. If the exhaust vents are connected to a ventilation system, make
sure that the material withstands high temperatures. Protect the resistor against
contact.
Selecting the resistor thermal switch circuit cable
Make sure that the cable in the resistor thermal switch circuit meets the following
requirements:
• shielded cable
• rated operating voltage between a core and ground > 750 (
U
0
)
• insulation test voltage > 2.5 kV
• jacket material for at least 90 °C (194 °F). Take into account further requirements due
to resistor construction and temperature.
Protecting the system against thermal overload
The brake control program includes a resistor and resistor cable thermal protection function,
which can be tuned by the user. The brake chopper protects itself and the resistor cables
against thermal overload. Make sure that the resistor assembly is equipped with a thermal
switch, which is wired to disable the chopper (and/or switch off the supply to the drive) in
case of overtemperature.
For more information on the thermal protection function, see the appropriate firmware
manual.
Protecting the system against short-circuits
The brake unit is equipped with fuses as standard.
The fuses protect the brake chopper, the brake resistor and the brake circuit cables in a
short-circuit situation.
Guidelines for planning the electrical installation 33
Summary of Contents for ACS880-607LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 607LC 3 phase dynamic brake units Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 30: ...30 ...
Page 34: ...34 ...
Page 46: ...46 ...
Page 56: ...56 ...
Page 72: ...7 After the module has drained disconnect the piping from the module 72 Maintenance ...
Page 88: ...88 ...
Page 95: ... Bottom entry and exit of cables Dimensions in mm 1 mm 0 0394 in Technical data 95 ...
Page 96: ...Dimensions in mm 1 mm 0 0394 in 96 Technical data ...
Page 97: ... Top entry and exit of cables Dimensions in mm 1 mm 0 0394 in Technical data 97 ...
Page 104: ...Brake unit with bottom exit Dimensions in mm 1 mm 0 0394 in 104 Dimension drawings ...
Page 105: ...Brake unit with top exit Dimensions in mm 1 mm 0 0394 in Dimension drawings 105 ...
Page 106: ...Bottom Top Dimensions in mm 1 mm 0 0394 in 106 Dimension drawings ...