Terminal data
For tightening torques of grounding terminals, see section
.
* Maximum cable diameter accepted.
Notes:
•
The minimum specified wire size does not necessarily have sufficient current carrying capacity at maximum load. Make
sure the installation complies with local laws and regulations.
•
For IEC installations using mm
2
cable,
the terminals do not accept a conductor that is one size larger than the
recommended wire size. For NEC installations using AWG cable, this applies only to the R8 frame 180A drive.
•
The maximum number of conductors per terminal is 1.
Dimensions, weights and free space requirements
1) for types -105A-3, 145A-3, -101A-5, -124A-5: 103 kg
2) for types -105A-3, 145A-3, -101A-5, -124A-5: 109 kg
3) for types -105A-3, 145A-3, -101A-5, -124A-5: 100 kg
4) for types -105A-3, 145A-3, -101A-5, -124A-5: 220 lb
200 mm (7.9 in) free space is required at top of the drive.
300 mm (11.8 in) free space (when measured from the drive base without the cable box) is required at bottom of the drive.
Ambient conditions
Frame
size
Cable entries
L1, L2, L3, T1/U, T2/V, T3/W, UDC+ and UDC- terminals
pcs
Max. cable diameter
*
Wire size
Tightening torque
mm
in
mm
2
AWG/kcmil
N·m
lbf·ft
R3
3
23
0.91
0.5…16.0
20…6
1.7
1.2
R6
3
45
1.77
6.0…70.0
6…1/0
15
11.0
R8
3
50
1.97
25…150
4…300 MCM
30
22.5
Frame size
Weight
Weight
Height
Height
Width
Width
Depth
Depth
kg
lb
mm
in
mm
in
mm
in
IP21 (UL Type 1)
R3
21.3
47
495
19.49
205
8.07
356
14.02
R6
61
135
771
30.35
252
9.92
382
15.03
R8
118
1)
260
965
38.01
300
11.81
430
16.94
IP55 (UL Type 12), B056
R3
23.3
51
495
19.49
205
8.07
360
14.17
R6
63
139
771
30.35
252
9.92
445
17.54
R8
124
2)
273
965
38.01
300
11.81
496
19.53
IP20 (UL Open Type), P940
R3
18.3
40.34
490
19
203
7.99
349
13.74
R6
59
131
771
30.35
252
9.92
358
14
R8
100-115
3)
254
4)
965
38.01
300
11.81
430
16.94
Installation altitude
0 … 4000 m (0 … 13123 ft) above sea level. The output current must be derated at
altitudes above 1000 m (3281 ft). The derating is 1% for each 100 m (328 ft) above
1000 m (3281 ft).
Surrounding air temperature
Operation: -15 … +55 °C (5 … 131 °F). Frost is not permitted. The rated output current
must be derated by 1% for each 1 °C (1.8 °F) over 40 °C (104 °F) except for IP55 (UL Type
12) drive type -206A-3, see the hardware manual.
Storage (in the package): -40 to +70 °C (-40 to +158 °F).