88 Maintenance
DC/DC converter module
Cleaning the module
The converter module heatsink fins pick up dust from the cooling air. Modules run into
overtemperature warnings and faults if the heatsink is not clean. When necessary, clean
the heatsink as follows.
WARNING!
Only qualified electricians are allowed to do this work. Read the
complete safety instructions given in
Safety instructions for ACS880 multidrive
cabinets and modules
(3AUA0000102301 [English]) before you service the drive.
If you ignore them, injury or death, or damage to the equipment can occur.
WARNING!
Wear protective gloves and long sleeves! Some parts have sharp
edges.
WARNING!
Use a vacuum cleaner with an antistatic hose and nozzle. Using a
normal vacuum cleaner creates static discharges which can damage circuit
boards.
1. Disconnect the drive from the AC power line and DC/DC converter from the energy
storage and obey the instructions in section
on page
See
Disconnecting the DC/DC converter with DC switch/disconnector (F286)
2. Remove the cooling fan of the converter module as described under section
this chapter.
3. Blow clean, dry and oilfree compressed air through the module from bottom to top,
simultaneously using a vacuum cleaner at the air outlet to trap the dust.
Note:
If there
is a risk of dust entering adjoining equipment, perform the cleaning in another room.
4. Refit the cooling fan.
Summary of Contents for ACS880-1607
Page 1: ...ABB industrial drives Hardware manual ACS880 1607 DC DC converter units ...
Page 4: ......
Page 12: ...12 Introduction to the manual ...
Page 34: ...34 Mechanical installation ...
Page 40: ...40 Guidelines for planning electrical installation ...
Page 52: ...52 Electrical installation ...
Page 68: ...68 Start up ...
Page 80: ...80 Maintenance 7 3 4 5 6 ...
Page 82: ...82 Maintenance 3 4 5 6 7 8 9 9 ...
Page 85: ...Maintenance 85 12 Install and tighten the two screws 10 11 12 ...
Page 92: ...92 Maintenance 3 6 4 5 4 7a 7b 7b ...
Page 93: ...Maintenance 93 9 8 8 10 11 ...
Page 96: ...96 Maintenance 4 8 6 7 5 3 ...
Page 97: ...Maintenance 97 9 ...
Page 118: ...118 Dimensions Dimension drawings Frame 1 R8i bottom cable entry ...
Page 119: ...Dimensions 119 Frame 1 R8i top cable entry ...
Page 122: ...www abb com drives www abb com drivespartners 3AXD50000023644 Rev B EN 2017 01 30 Contact us ...