ABB ACS880-01 Series Quick Installation And Start-Up Manual Download Page 9

   9

Connection procedure with conduit

1.

Connect the power cables. ABB recommends symmetrically shielded VFD cable for connecting the motor.

Attach the residual voltage warning sticker and remove the covers as instructed in 

Connection procedure with VFD 

cable

.

Remove the rubber grommets from the conduit plate for the conduit to be connected. 

Attach the conduit to the drive conduit plate, and to the motor or source of power distribution. Make sure conduit is 

correctly bonded at both ends of the conduit. Ensure conductivity of the conduit. Slide the VFD shielded cable or 

discrete conductors through the conduit and strip the cable ends.

If you use a symmetrically shielded VFD cable, twist

 

the grounding wires together with the cable shield and connect 

them to the grounding terminals. Ground the shield 360 degrees at the grounding clamp. If you use discrete 

conductors connect the insulated ground conductor to the ground terminal.

Connect the input and motor conductors and tighten cable terminals

For the tightening torques, refer to 

Terminal 

data

.

Frames R4, R5: Install the EMC shroud separating the input and output cabling if not installed yet.

If brake chopper is in use: Connect the brake resistor conductors to the R+ and R- terminals.

 Reinstall the shroud on the power cable terminals.

2. Connect the control cables

Attach the cable conduits to the drive conduit plate. Make sure conduit is correctly bonded at both ends and that the 

conductivity is consistent throughout the conduit. Slide the control cables through the conduit.

Cut to suitable length (note the extra length of the grounding conductors) and strip the conductors.

Ground the outer shields of all control cables 360 degrees at a grounding clamp.

Ground the pair-cable shields to the grounding clamp. Use an unused ground clamp screw. If none available ground 

as shown.

 

Leave the other end of the shields unconnected or ground them indirectly via a high-frequency capacitor 

with a few nanofarads, eg, 3.3 nF / 630 V.

Connect the conductors to the appropriate terminals of the control unit.

Wire the optional modules if included in the delivery. 

Reinstall the front covers as instructed in 

Install the cover(s)

.

4

5 lbf·in 

13 lbf·in
M4×20 Torx T20

1

1

3

13 lbf·in

M4×20 Torx T20

PE

Summary of Contents for ACS880-01 Series

Page 1: ...After unpacking protect the drive from dust debris and moisture Make sure that these items are included cable conduit box frames R5 R9 of IP21 UL Type 1 drive mounting template control panel quick ins...

Page 2: ...erial The installation surface is as close to vertical as possible and strong enough to support the drive There is sufficient free space around the drive for cooling maintenance and operation For the...

Page 3: ...the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and midpoint grounded delta systems IT systems ungrounded or high resistance grounded TT syste...

Page 4: ...e c Shield of a VFD shielded cable Ground the shield 360 under drive s grounding clamp then twist with the ground conductors and connect under the drive s ground terminal Ground the shield also 360 a...

Page 5: ...to Terminal data For frames R1 R3 Ground the cable shields 360 degrees in the Romex clamp IP21 Type 1 units For IP55 Type 12 ground the cable shield 360 degrees on grounding shelf as shown in R4 R5 a...

Page 6: ...als as possible to prevent inductive coupling 1 Cut a hole into the rubber grommet and slide the grommet onto the cable 2 Ground the outer shield of the cable 360 degrees under the grounding clamp Kee...

Page 7: ...22 COM 23 NO 31 NC Faulted 1 250 V AC 30 V DC 2 A 32 COM 33 NO XD24 Digital interlock 1 DIIL Run enable 2 24VD 24 V DC 200 mA 1 3 DICOM Digital input ground 4 24VD 24 V DC 200 mA 1 5 DIOGND Digital in...

Page 8: ...1 5 N m 1 5 N m R1 R3 R4 R9 Note Use an un used ground clamp screw If none available ground as shown 1 2 3 2 2 Note The illustration shows frame R2 All frame sizes are similar M4 8 Torx T20 2 N m 17 l...

Page 9: ...torques refer to Terminal data Frames R4 R5 Install the EMC shroud separating the input and output cabling if not installed yet If brake chopper is in use Connect the brake resistor conductors to the...

Page 10: ...xt Use the arrow keys and to move the cursor or change values depending on the active view Key shows a context sensitive help page 1 Power up the drive Make sure that you have the motor name plate dat...

Page 11: ...in the master station 58 05 Parity 8 EVEN 1 default Selects the parity and stop bit setting Use the same setting as in the master station 58 06 Communication control Refresh settings Validates any ch...

Page 12: ...880 01 Frame size Nominal ratings Fuses3 Typical power cable Typical power loss 8 Input current Output current Motor power1 gG fuse4 DIN 43620 aR fuse2 4 DIN 43620 ULclass T5 6 7 Copper I1 I2 Pn ABB t...

Page 13: ...0 170M6814D JJS 500 2 3 120 2 4 0 4800 414A 5 R9 414 414 250 350 OFAF3H630 170M8554D JJS 600 2 3 150 2 300 MCM 5662 Un 3 phase 575 V 07A4 7 R3 7 0 7 0 5 0 JJS 15 14 106 09A9 7 R3 9 4 9 4 7 5 JJS 20 14...

Page 14: ...M 30 22 1 185 350 MCM 9 8 7 2 R7 1 54 2 13 95 240 25 150 3 0 400 MCM 4 300 MCM 40 30 29 5 22 1 185 350 MCM 9 8 7 2 R8 2 45 1 77 2 50 150 2 1 0 300 MCM 40 29 5 2 185 2 350 MCM 9 8 7 2 R9 2 54 2 13 2 95...

Page 15: ...ledge of the safety function The test procedures and report must be documented and signed by this person Validation instructions of the STO function can be found in the drive hardware manual Technical...

Page 16: ...ucts ACS880 01 11 31 ACS880 04 04F M04 14 34 Safe Torque Off Safe stop 1 Safe stop emergency Safely limited speed Safe maximum speed Safe brake control Prevention of unexpected start up with FSO 12 op...

Reviews: