ABB ACS880-01 Series Quick Installation And Start-Up Manual Download Page 4

   4

9.  Connect the power cables

IEC connection diagram with shielded cables

NEC connection diagram with symmetrically shielded cable or conduit

Connection procedure with VFD cable

For connection procedure with conduits, see 

Connection 

procedure with conduit

Attach a residual voltage warning sticker in the local language:
Frames R1…R3: to the control panel mounting platform
Frames R4, R5: next to the control unit top
Frames R6…R9: next to the control unit.

b. Use a separate grounding cable or a cable 

with a separate PE conductor for the line 

side, if the conductivity of the fourth 

conductor or shield does not meet the 

requirements for the PE conductor.

c. Use a separate grounding cable for the 

motor side, if the conductivity of the shield 

is not sufficient, or if there is no 

symmetrically constructed PE conductor in 

the cable.

d. 360-degree grounding of the cable shield is 

required for the motor cable and brake 

resistor cable (if used). It is also 

recommended for the input power cable.

e. If necessary, install an external filter (du/dt, 

common mode, or sine filter). Filters are 

available from ABB.

Frames R1…R4 have a built-in brake chopper 

as standard. Frames R5 and up can be 

equipped with optional built-in brake chopper 

(+D150). Brake resistors are available as add-

on kits.

a. Two protective earth (ground) conductors. Drive safety standard IEC/

EN 61800-5-1 requires two PE conductors, if the cross-sectional area 

of the PE conductor is less than 10 mm

2

 Cu or 16 mm

2

 Al. For example, 

you can use the cable shield in addition to the fourth conductor. 

PE

PE

L1

L2

L3

R- R+

UDC+

U1

W1

M

3

T1/U T2/V T3/W

V1

(PE)

(PE)

L1

L2

L3

PE

UDC-

a

b

d

d

c

d

e

c. Shield of a VFD shielded cable: Ground the 

shield 360° under drive's grounding clamp, 

then twist with the ground conductors and 

connect under the drive's ground terminal. 

Ground the shield also 360° at the motor end, 

then twist and connect under the motor's 

ground terminal. For a conduit installation 

see b.

d. Symmetrically constructed grounding 

conductors inside a VFD shielded cable: 

Twist together, combine with the shield and 

connect under the drive's ground terminal 

and under the motor's ground terminal. For a 

conduit installation see a.

 

e. External brake resistor connection (if used): 

For a conduit installation see a and b. For a 

VFD cable installation see c and d. In 

addition, cut the third phase conductor 

which is not needed for the brake resistor 

connection.

f. If necessary, install an external filter (du/dt, 

common mode, or sine filter). Filters are 

available from ABB.

Frames R1…R4 have a built-in brake chopper as 

standard. Frames R5 and up can be equipped 

with optional built-in brake chopper (+D150). 

Brake resistors are available as add-on kits.

Note:

 All openings in the drive enclosure must 

be closed with UL listed devices having the 

same Type rating as the drive Type.

Note:

 NEC installation can include separate insulated conductors 

inside a conduit, shielded VFD cable in conduit, or shielded VFD cable 

without conduit. The normal dashed symbol (c) in this diagram 

represents the shield of shielded VFD cable. The same solid symbol (b) 

represents conduit.

a. Insulated ground conductor in a conduit: Ground to drive's PE 

terminal and to the distribution panel ground bus. For a VFD cable 

installation see d.

b. Conduit ground: Bond the conduit to the drive's conduit box and to 

the distribution panel enclosure. For a VFD cable installation see c

.

PE

PE

L1

L2

L3

R-

U1

W1

M

3

T1/U T2/V T3/W

V1

L1

L2

L3

PE

3

UDC-

R+

UDC+

a

b

c

d

d

e

f

Summary of Contents for ACS880-01 Series

Page 1: ...After unpacking protect the drive from dust debris and moisture Make sure that these items are included cable conduit box frames R5 R9 of IP21 UL Type 1 drive mounting template control panel quick ins...

Page 2: ...erial The installation surface is as close to vertical as possible and strong enough to support the drive There is sufficient free space around the drive for cooling maintenance and operation For the...

Page 3: ...the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and midpoint grounded delta systems IT systems ungrounded or high resistance grounded TT syste...

Page 4: ...e c Shield of a VFD shielded cable Ground the shield 360 under drive s grounding clamp then twist with the ground conductors and connect under the drive s ground terminal Ground the shield also 360 a...

Page 5: ...to Terminal data For frames R1 R3 Ground the cable shields 360 degrees in the Romex clamp IP21 Type 1 units For IP55 Type 12 ground the cable shield 360 degrees on grounding shelf as shown in R4 R5 a...

Page 6: ...als as possible to prevent inductive coupling 1 Cut a hole into the rubber grommet and slide the grommet onto the cable 2 Ground the outer shield of the cable 360 degrees under the grounding clamp Kee...

Page 7: ...22 COM 23 NO 31 NC Faulted 1 250 V AC 30 V DC 2 A 32 COM 33 NO XD24 Digital interlock 1 DIIL Run enable 2 24VD 24 V DC 200 mA 1 3 DICOM Digital input ground 4 24VD 24 V DC 200 mA 1 5 DIOGND Digital in...

Page 8: ...1 5 N m 1 5 N m R1 R3 R4 R9 Note Use an un used ground clamp screw If none available ground as shown 1 2 3 2 2 Note The illustration shows frame R2 All frame sizes are similar M4 8 Torx T20 2 N m 17 l...

Page 9: ...torques refer to Terminal data Frames R4 R5 Install the EMC shroud separating the input and output cabling if not installed yet If brake chopper is in use Connect the brake resistor conductors to the...

Page 10: ...xt Use the arrow keys and to move the cursor or change values depending on the active view Key shows a context sensitive help page 1 Power up the drive Make sure that you have the motor name plate dat...

Page 11: ...in the master station 58 05 Parity 8 EVEN 1 default Selects the parity and stop bit setting Use the same setting as in the master station 58 06 Communication control Refresh settings Validates any ch...

Page 12: ...880 01 Frame size Nominal ratings Fuses3 Typical power cable Typical power loss 8 Input current Output current Motor power1 gG fuse4 DIN 43620 aR fuse2 4 DIN 43620 ULclass T5 6 7 Copper I1 I2 Pn ABB t...

Page 13: ...0 170M6814D JJS 500 2 3 120 2 4 0 4800 414A 5 R9 414 414 250 350 OFAF3H630 170M8554D JJS 600 2 3 150 2 300 MCM 5662 Un 3 phase 575 V 07A4 7 R3 7 0 7 0 5 0 JJS 15 14 106 09A9 7 R3 9 4 9 4 7 5 JJS 20 14...

Page 14: ...M 30 22 1 185 350 MCM 9 8 7 2 R7 1 54 2 13 95 240 25 150 3 0 400 MCM 4 300 MCM 40 30 29 5 22 1 185 350 MCM 9 8 7 2 R8 2 45 1 77 2 50 150 2 1 0 300 MCM 40 29 5 2 185 2 350 MCM 9 8 7 2 R9 2 54 2 13 2 95...

Page 15: ...ledge of the safety function The test procedures and report must be documented and signed by this person Validation instructions of the STO function can be found in the drive hardware manual Technical...

Page 16: ...ucts ACS880 01 11 31 ACS880 04 04F M04 14 34 Safe Torque Off Safe stop 1 Safe stop emergency Safely limited speed Safe maximum speed Safe brake control Prevention of unexpected start up with FSO 12 op...

Reviews: