Ratings, fuses and typical power cables

1) Typical motor power with no overload capacity (nominal use). The kilowatt ratings apply to most IEC 4-pole motors. The
horsepower ratings apply to most NEMA 4-pole motors.
2) For IEC installations, ABB recommends aR fuses. See hardware manual for guidelines in selecting between aR and gG 

fuses, and for additional fuse alternatives

.

3) The recommended branch protection fuses must be used to maintain the IEC/EN/UL 61800-5-1 and CSA C22.2 No. 274 

certifications. Refer to note 6 for circuit breaker protection.
4) IEC 61439-1:

 

The drive is suitable for use on a circuit capable of delivering not more than 65 kA

 

when protected by the 

fuses given in this table. 
5) UL 61800-5-1, CSA C22.2 No. 274: The drive is suitable for use on a circuit capable of delivering not more than 100 kA 

symmetrical amperes (rms) at 600 V maximum when protected by the ABB recommended fuses.
6) Refer to 

Alternate Fuses, MMPs and Circuit Breakers for ABB Drives

 (

3AXD50000645015

 [English]) for additional UL fuses 

and circuit breakers that can be used as branch circuit protection. 
7) Class J, CC, and CF fuses are also allowed at the same nominal current and voltage ratings.
8)IEC 61800-9-2: Typical drive losses when it operates at 90% of the nominal output frequency and 100% of the nominal 

output current.
9) IEC Installations: The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one 

on top of the other, ambient temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-

52/2001). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load 

current of the drive.
10) NEC Installations:

 

The cable sizing is based on NEC Table 310-15 for copper wires, 75 °C (167 °F) wire insulation at 40 °C 

(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly 

buried). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load 

current of the drive.

-

FA81

Safe torque off 1 loss

The Safe torque off circuit 1 is broken.

-

FA82

Safe torque off 2 loss

The Safe torque off circuit 2 is broken.

ACS880

-01-…

Frame 

size

Nominal ratings

Fuses

3)

Typical power cable

Typical 

power loss 

8)

Input 

current

Output 

current

Motor 

power

1)

gG fuse

4)

(DIN 43620)

aR fuse

2)4)

 

(DIN 43620)

UL class 

T

5)6)7)

Copper

I

1

I

2

P

n

ABB type

Bussmann type

mm

2  9)

AWG 

10)

W

A

A

kW

hp

U

n

 = 3-phase 230 V

04A6-2

R1

4.6

4.6

0.75

1.0

OFAF000H6

170M1559

JJS-15

3×1.5

14

61

06A6-2

R1

6.6

6.6

1.1

1.5

OFAF000H10

170M1559

JJS-15

3×1.5

14

88

07A5-2

R1

7.5

7.5

1.5

2.0

OFAF000H16

170M1559

JJS-15

3×1.5

14

100

10A6-2

R1

10.6

10.6

2.2

3.0

OFAF000H16

170M1560

JJS-20

3×1.5

14

152

16A8-2

R2

16.8

16.8

4.0

5.0

OFAF000H25

170M1561

JJS-25

3×6

10

216

24A3-2

R2

24.3

24.3

5.5

7.5

OFAF000H40

170M1563

JJS-35

3×6

8

372

031A-2

R3

31.0

31.0

7.5

10

OFAF000H50

170M1565

JJS-50

3×10

8

364

046A-2

R4

46

46

11

11

OFAF000H63

170M1566

JJS-80

3×16

6

551

061A-2

R4

61

61

15

20

OFAF000H80

170M1568

JJS-80

3×25

4

811

075A-2

R5

75

75

18.5

25

OFAF000H100

170M3815

JJS-110

3×35

3

955

087A-2

R5

87

87

22

30

OFAF00H125

170M3816

JJS-110

3×35

2

1177

115A-2

R6

115

115

30

40

OFAF00H160

170M3817

JJS-150

3×50

1/0

1378

145A-2

R6

145

145

37

50

OFAF0H200

170M3817

JJS-200

3×95

3/0

1946

170A-2

R7

170

170

45

60

OFAF0H250

170M5809

JJS-250

3×120

4/0

1986

206A-2

R7

206

206

55

75

OFAF1H315

170M5810

JJS-300

2×150

300 MCM

2660

274A-2

R8

274

274

75

100

OFAF2H400

170M5810

JJS-400 2×(3×95)

2×2/0

3472

U

n

 = 3-phase 400 V

02A4-3

R1

2.4

2.4

0.75

-

OFAF000H4

170M1561

-

3×1.5

-

47

03A3-3

R1

3.3

3.3

1.1

-

OFAF000H6

170M1561

-

3×1.5

-

55

04A0-3

R1

4.0

4.0

1.5

-

OFAF000H6

170M1561

-

3×1.5

-

63

05A6-3

R1

5.6

5.6

2.2

-

OFAF000H10

170M1561

-

3×1.5

-

81

07A2-3

R1

8.0

8.0

3.0

-

OFAF000H10

170M1561

-

3×1.5

-

115

09A4-3

R1

10.0

10.0

4.0

-

OFAF000H16

170M1561

-

3×1.5

-

149

12A6-3

R1

12.9

12.9

5.5

-

OFAF000H16

170M1561

-

3×1.5

-

217

017A-3

R2

17.0

17.0

7.5

-

OFAF000H25

170M1563

-

3×6

-

239

025A-3

R2

25.0

25.0

11.0

-

OFAF000H32

170M1563

-

3×6

-

411

032A-3

R3

32.0

32.0

15.0

-

OFAF000H40

170M1565

-

3×10

-

406

038A-3

R3

38.0

38.0

18.5

-

OFAF000H50

170M1565

-

3×10

-

519

045A-3

R4

45.0

45.0

22.0

-

OFAF000H63

170M1566

-

3×16

-

533

061A-3

R4

61

61

30

-

OFAF000H80

170M1567

-

3×25

-

820

072A-3

R5

72

72

37

-

OFAF000H100

170M1568

-

3×35

-

865

087A-3

R5

87

87

45

-

OFAF000H100

170M1569

-

3×35

-

1157

105A-3

R6

105

105

55

-

OFAF00H125

170M3817

-

3×50

-

1228

145A-3

R6

145

145

75

-

OFAF00H160

170M3817

-

3×95

-

1965

169A-3

R7

169

169

90

-

OFAF0H250

170M5809

-

3×120

-

2049

206A-3

R7

206

206

110

-

OFAF1H315

170M5810

-

3×150

-

2812

246A-3

R8

246

246

132

-

OFAF1H355

170M5812

-

2×(3×70)

-

3049

Warning

Fault Aux. code

Description

Summary of Contents for ACS880-01 Series

Page 1: ...After unpacking protect the drive from dust debris and moisture Make sure that these items are included cable conduit box frames R5 R9 of IP21 UL Type 1 drive mounting template control panel quick ins...

Page 2: ...erial The installation surface is as close to vertical as possible and strong enough to support the drive There is sufficient free space around the drive for cooling maintenance and operation For the...

Page 3: ...the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and midpoint grounded delta systems IT systems ungrounded or high resistance grounded TT syste...

Page 4: ...e c Shield of a VFD shielded cable Ground the shield 360 under drive s grounding clamp then twist with the ground conductors and connect under the drive s ground terminal Ground the shield also 360 a...

Page 5: ...to Terminal data For frames R1 R3 Ground the cable shields 360 degrees in the Romex clamp IP21 Type 1 units For IP55 Type 12 ground the cable shield 360 degrees on grounding shelf as shown in R4 R5 a...

Page 6: ...als as possible to prevent inductive coupling 1 Cut a hole into the rubber grommet and slide the grommet onto the cable 2 Ground the outer shield of the cable 360 degrees under the grounding clamp Kee...

Page 7: ...22 COM 23 NO 31 NC Faulted 1 250 V AC 30 V DC 2 A 32 COM 33 NO XD24 Digital interlock 1 DIIL Run enable 2 24VD 24 V DC 200 mA 1 3 DICOM Digital input ground 4 24VD 24 V DC 200 mA 1 5 DIOGND Digital in...

Page 8: ...1 5 N m 1 5 N m R1 R3 R4 R9 Note Use an un used ground clamp screw If none available ground as shown 1 2 3 2 2 Note The illustration shows frame R2 All frame sizes are similar M4 8 Torx T20 2 N m 17 l...

Page 9: ...torques refer to Terminal data Frames R4 R5 Install the EMC shroud separating the input and output cabling if not installed yet If brake chopper is in use Connect the brake resistor conductors to the...

Page 10: ...xt Use the arrow keys and to move the cursor or change values depending on the active view Key shows a context sensitive help page 1 Power up the drive Make sure that you have the motor name plate dat...

Page 11: ...in the master station 58 05 Parity 8 EVEN 1 default Selects the parity and stop bit setting Use the same setting as in the master station 58 06 Communication control Refresh settings Validates any ch...

Page 12: ...880 01 Frame size Nominal ratings Fuses3 Typical power cable Typical power loss 8 Input current Output current Motor power1 gG fuse4 DIN 43620 aR fuse2 4 DIN 43620 ULclass T5 6 7 Copper I1 I2 Pn ABB t...

Page 13: ...0 170M6814D JJS 500 2 3 120 2 4 0 4800 414A 5 R9 414 414 250 350 OFAF3H630 170M8554D JJS 600 2 3 150 2 300 MCM 5662 Un 3 phase 575 V 07A4 7 R3 7 0 7 0 5 0 JJS 15 14 106 09A9 7 R3 9 4 9 4 7 5 JJS 20 14...

Page 14: ...M 30 22 1 185 350 MCM 9 8 7 2 R7 1 54 2 13 95 240 25 150 3 0 400 MCM 4 300 MCM 40 30 29 5 22 1 185 350 MCM 9 8 7 2 R8 2 45 1 77 2 50 150 2 1 0 300 MCM 40 29 5 2 185 2 350 MCM 9 8 7 2 R9 2 54 2 13 2 95...

Page 15: ...ledge of the safety function The test procedures and report must be documented and signed by this person Validation instructions of the STO function can be found in the drive hardware manual Technical...

Page 16: ...ucts ACS880 01 11 31 ACS880 04 04F M04 14 34 Safe Torque Off Safe stop 1 Safe stop emergency Safely limited speed Safe maximum speed Safe brake control Prevention of unexpected start up with FSO 12 op...

Reviews: