Ratings, fuses and typical power cables
1) Typical motor power with no overload capacity (nominal use). The kilowatt ratings apply to most IEC 4-pole motors. The
horsepower ratings apply to most NEMA 4-pole motors.
2) For IEC installations, ABB recommends aR fuses. See hardware manual for guidelines in selecting between aR and gG
fuses, and for additional fuse alternatives
.
3) The recommended branch protection fuses must be used to maintain the IEC/EN/UL 61800-5-1 and CSA C22.2 No. 274
certifications. Refer to note 6 for circuit breaker protection.
4) IEC 61439-1:
The drive is suitable for use on a circuit capable of delivering not more than 65 kA
when protected by the
fuses given in this table.
5) UL 61800-5-1, CSA C22.2 No. 274: The drive is suitable for use on a circuit capable of delivering not more than 100 kA
symmetrical amperes (rms) at 600 V maximum when protected by the ABB recommended fuses.
6) Refer to
Alternate Fuses, MMPs and Circuit Breakers for ABB Drives
(
[English]) for additional UL fuses
and circuit breakers that can be used as branch circuit protection.
7) Class J, CC, and CF fuses are also allowed at the same nominal current and voltage ratings.
8)IEC 61800-9-2: Typical drive losses when it operates at 90% of the nominal output frequency and 100% of the nominal
output current.
9) IEC Installations: The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-
52/2001). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load
current of the drive.
10) NEC Installations:
The cable sizing is based on NEC Table 310-15 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly
buried). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load
current of the drive.
-
FA81
Safe torque off 1 loss
The Safe torque off circuit 1 is broken.
-
FA82
Safe torque off 2 loss
The Safe torque off circuit 2 is broken.
ACS880
-01-…
Frame
size
Nominal ratings
Fuses
3)
Typical power cable
Typical
power loss
8)
Input
current
Output
current
Motor
power
1)
gG fuse
4)
(DIN 43620)
aR fuse
2)4)
(DIN 43620)
UL class
T
5)6)7)
Copper
I
1
I
2
P
n
ABB type
Bussmann type
mm
2 9)
AWG
10)
W
A
A
kW
hp
U
n
= 3-phase 230 V
04A6-2
R1
4.6
4.6
0.75
1.0
OFAF000H6
170M1559
JJS-15
3×1.5
14
61
06A6-2
R1
6.6
6.6
1.1
1.5
OFAF000H10
170M1559
JJS-15
3×1.5
14
88
07A5-2
R1
7.5
7.5
1.5
2.0
OFAF000H16
170M1559
JJS-15
3×1.5
14
100
10A6-2
R1
10.6
10.6
2.2
3.0
OFAF000H16
170M1560
JJS-20
3×1.5
14
152
16A8-2
R2
16.8
16.8
4.0
5.0
OFAF000H25
170M1561
JJS-25
3×6
10
216
24A3-2
R2
24.3
24.3
5.5
7.5
OFAF000H40
170M1563
JJS-35
3×6
8
372
031A-2
R3
31.0
31.0
7.5
10
OFAF000H50
170M1565
JJS-50
3×10
8
364
046A-2
R4
46
46
11
11
OFAF000H63
170M1566
JJS-80
3×16
6
551
061A-2
R4
61
61
15
20
OFAF000H80
170M1568
JJS-80
3×25
4
811
075A-2
R5
75
75
18.5
25
OFAF000H100
170M3815
JJS-110
3×35
3
955
087A-2
R5
87
87
22
30
OFAF00H125
170M3816
JJS-110
3×35
2
1177
115A-2
R6
115
115
30
40
OFAF00H160
170M3817
JJS-150
3×50
1/0
1378
145A-2
R6
145
145
37
50
OFAF0H200
170M3817
JJS-200
3×95
3/0
1946
170A-2
R7
170
170
45
60
OFAF0H250
170M5809
JJS-250
3×120
4/0
1986
206A-2
R7
206
206
55
75
OFAF1H315
170M5810
JJS-300
2×150
300 MCM
2660
274A-2
R8
274
274
75
100
OFAF2H400
170M5810
JJS-400 2×(3×95)
2×2/0
3472
U
n
= 3-phase 400 V
02A4-3
R1
2.4
2.4
0.75
-
OFAF000H4
170M1561
-
3×1.5
-
47
03A3-3
R1
3.3
3.3
1.1
-
OFAF000H6
170M1561
-
3×1.5
-
55
04A0-3
R1
4.0
4.0
1.5
-
OFAF000H6
170M1561
-
3×1.5
-
63
05A6-3
R1
5.6
5.6
2.2
-
OFAF000H10
170M1561
-
3×1.5
-
81
07A2-3
R1
8.0
8.0
3.0
-
OFAF000H10
170M1561
-
3×1.5
-
115
09A4-3
R1
10.0
10.0
4.0
-
OFAF000H16
170M1561
-
3×1.5
-
149
12A6-3
R1
12.9
12.9
5.5
-
OFAF000H16
170M1561
-
3×1.5
-
217
017A-3
R2
17.0
17.0
7.5
-
OFAF000H25
170M1563
-
3×6
-
239
025A-3
R2
25.0
25.0
11.0
-
OFAF000H32
170M1563
-
3×6
-
411
032A-3
R3
32.0
32.0
15.0
-
OFAF000H40
170M1565
-
3×10
-
406
038A-3
R3
38.0
38.0
18.5
-
OFAF000H50
170M1565
-
3×10
-
519
045A-3
R4
45.0
45.0
22.0
-
OFAF000H63
170M1566
-
3×16
-
533
061A-3
R4
61
61
30
-
OFAF000H80
170M1567
-
3×25
-
820
072A-3
R5
72
72
37
-
OFAF000H100
170M1568
-
3×35
-
865
087A-3
R5
87
87
45
-
OFAF000H100
170M1569
-
3×35
-
1157
105A-3
R6
105
105
55
-
OFAF00H125
170M3817
-
3×50
-
1228
145A-3
R6
145
145
75
-
OFAF00H160
170M3817
-
3×95
-
1965
169A-3
R7
169
169
90
-
OFAF0H250
170M5809
-
3×120
-
2049
206A-3
R7
206
206
110
-
OFAF1H315
170M5810
-
3×150
-
2812
246A-3
R8
246
246
132
-
OFAF1H355
170M5812
-
2×(3×70)
-
3049
Warning