20 Control locations and operating modes
Local control vs. external control
The ACS860 has two main control locations: external and local. The control location
is selected with the Loc/Rem key on the control panel or in the PC tool.
Local control
The control commands are given from the control panel keypad or from a PC
equipped with Drive composer when the drive is set to local control. Speed and
torque control modes are available for local control; frequency mode is available
when scalar motor control mode is used (see parameter
).
Local control is mainly used during commissioning and maintenance. The control
panel always overrides the external control signal sources when used in local control.
Changing the control location to local can be prevented by parameter
.
The user can select by a parameter (
) how the drive
reacts to a control panel or PC tool communication break. (The parameter has no
effect in external control.)
Control panel or Drive
composer PC tool (optional)
Fieldbus adapter (Fxxx)
or DDCS communication
module
1) Encoder or resolver interface module(s) (FEN-xx) installed in drive slot 1.
MOTOR
PLC
M
3~
Embedded fieldbus
interface (EFB) or
master/follower link
External control
Local control
Encoder
1)
ACS860
Control panel
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...