Parameters 189
Add
Sum of feedback 1 and feedback 2.
1
Sub
Feedback 2 subtracted from feedback 1.
2
Mul
Feedback 1 multiplied by feedback 2.
3
div
Feedback 1 divided by feedback 2.
4
Max
Greater of the two feedback sources used.
5
Min
Smaller of the two feedbacks sources used.
6
Sqrt sub
Square root of (feedback 1 – feedback 2).
7
Sqrt add
Square root of feedback 1 + square root of feedback 2.
8
27.03
PID fbk1 src
Selects the source of process feedback 1.
Zero
Zero feedback.
0
AI1 scaled
(see page
).
1073742341
AI2 scaled
(see page
).
1073742343
FBA ref1
1073742362
FBA ref2
1073742363
D2D ref1
(see page
).
1073742368
D2D ref2
(see page
).
1073742369
Pointer
on page
).
-
27.04
PID fbk2 src
Selects the source of process feedback 2.
Zero
Zero feedback.
0
AI1 scaled
(see page
).
1073742341
AI2 scaled
(see page
).
1073742343
FBA ref1
1073742362
FBA ref2
1073742363
D2D ref1
(see page
).
1073742368
D2D ref2
(see page
).
1073742369
Pointer
on page
).
-
27.05
PID fbk1 max
Maximum value for process feedback 1.
-32768.00 …
32768.00
Maximum value for process feedback 1.
100 = 1
27.06
PID fbk1 min
Minimum value for process feedback 1.
-32768.00 …
32768.00
Minimum value for process feedback 1.
100 = 1
27.07
PID fbk2 max
Maximum value for process feedback 2.
-32768.00 …
32768.00
Maximum value for process feedback 2.
100 = 1
27.08
PID fbk2 min
Minimum value for process feedback 2.
-32768.00 …
32768.00
Minimum value for process feedback 2.
100 = 1
27.09
PID fbk gain
Multiplier for scaling the final feedback value for process PID
controller.
-32.768 … 32.767
PID feedback gain.
1000 = 1
No.
Name/Value
Description
FbEq
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...