Parameters 105
02.03
DIO status
Status of digital input/outputs DIO10…DIO1.
Example:
0000001001 = DIO1 and DIO4 are on, remainder are off.
DIO3…DIO10 are available only with FIO I/O extension
modules.
-
02.04
AI1
Value of analogue input AI1 in V or mA. Input type is selected
with jumper J1 on the JCU Control Unit.
1000 = 1 unit
02.05
AI1 scaled
Scaled value of analogue input AI1. See parameters
and
.
1000 = 1 unit
02.06
AI2
Value of analogue input AI2 in V or mA. Input type is selected
with jumper J2 on the JCU Control Unit.
1000 = 1 unit
02.07
AI2 scaled
Scaled value of analogue input AI2. See parameters
and
.
1000 = 1 unit
02.08
AI3
Value of analogue input AI3 in V or mA. For input type
information, see the extension module manual.
1000 = 1 unit
02.09
AI3 scaled
Scaled value of analogue input AI3. See parameters
and
.
1000 = 1 unit
02.10
AI4
Value of analogue input AI4 in V or mA. For input type
information, see the extension module manual.
1000 = 1 unit
02.11
AI4 scaled
Scaled value of analogue input AI4. See parameters
and
.
1000 = 1 unit
02.12
AI5
Value of analogue input AI5 in V or mA. For input type
information, see the extension module manual.
1000 = 1 unit
02.13
AI5 scaled
Scaled value of analogue input AI5. See parameters
and
.
1000 = 1 unit
02.14
AI6
Value of analogue input AI6 in V or mA. For input type
information, see the extension module manual.
1000 = 1 unit
02.15
AI6 scaled
Scaled value of analogue input AI6. See parameters
and
.
1000 = 1 unit
02.16
AO1
Value of analogue output AO1 in mA.
1000 = 1 mA
02.17
AO2
Value of analogue output AO2 in mA.
1000 = 1 mA
02.18
AO3
Value of analogue output AO3 in mA.
1000 = 1 mA
02.19
AO4
Value of analogue output AO4 in mA.
1000 = 1 mA
02.20
Freq in
Scaled value of DIO1 when it is used as a frequency input.
See parameters
1000 = 1
02.21
Freq out
Frequency output value of DIO2 when it is used as a
frequency output (parameter
is set to
1000 = 1 Hz
No.
Name/Value
Description
FbEq
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...