Parameters 153
14.57
Freq in max
Defines the maximum input frequency for DIO1 when
parameter
.
The frequency signal connected to DIO1 is scaled into an
internal signal (
) by parameters
as
follows:
3 … 32768 Hz
DIO1 maximum frequency.
1 = 1 Hz
14.58
Freq in min
Defines the minimum input frequency for DIO1 when
parameter
. See
parameter
.
3 … 32768 Hz
DIO1 minimum frequency.
1 = 1 Hz
14.59
Freq in max scal
Defines the value that corresponds to the maximum input
frequency defined by parameter
parameter
.
-32768 … 32768
Scaled value corresponding to DIO1 maximum frequency.
1 = 1
14.60
Freq in min scal
Defines the value that corresponds to the minimum input
frequency defined by parameter
. See
parameter
.
-32768 … 32768
Scaled value corresponding to DIO1 minimum frequency.
1 = 1
14.61
Freq out src
Selects a drive signal to be connected to frequency output
DIO2 (when
is set to
).
Pointer
on page
).
-
No.
Name/Value
Description
FbEq
f
DIO1
(Hz)