Parameters 109
02.26
FBA main ref1
Internal and scaled reference 1 of the drive received through
the fieldbus adapter interface. See parameter
Control through a fieldbus adapter
on
page
.
1 = 1
02.27
FBA main ref2
Internal and scaled reference 2 of the drive received through
the fieldbus adapter interface. See parameter
Control through a fieldbus adapter
on
page
.
1 = 1
02.30
D2D main cw
Drive-to-drive control word received from the master. See
also actual signal
.
-
No.
Name/Value
Description
FbEq
Bit
Name
Value Information
(continued)
9
Limit
1
Operation is limited by any of the torque limits.
0
Operation is within the torque limits.
10
Above limit
1
Actual speed exceeds limit defined by parameter
.
0
Actual speed is within the defined limits.
11
Ext2 act
1
External control location EXT2 is active.
0
External control location EXT1 is active.
12
Local fb
1
Fieldbus local control is active.
0
Fieldbus local control is inactive.
13
Zero
speed
1
Drive speed is below limit defined by parameter
0
Drive has not reached zero speed limit.
14
Rev act
1
Drive is running in reverse direction.
0
Drive is running in forward direction.
15
Reserved
16
Fault
1
A fault is active. See chapter
on page
.
0
No fault is active.
17
Local
panel
1
Local control is active, i.e. the drive is controlled from PC tool or
control panel.
0
Local control is inactive.
18…26 Reserved
27
Request ctl
1
Control Word is requested from fieldbus.
0
Control Word is not requested from fieldbus.
28
SW B28
Programmable control bits (unless fixed by the used profile). See parameters
and the user manual of the fieldbus adapter.
29
SW B29
30
SW B30
31
SW B31
Bit
Information
0
Stop.
1
Start.
2 … 6
Reserved.
7
Run enable. By default, not connected in a follower drive.
8
Reset. By default, not connected in a follower drive.
9 … 14 Freely assignable through bit pointer settings.
15
EXT1/EXT2 selection. 0 = EXT1 active, 1 = EXT2 active. By default, not connected in a
follower drive.
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...