136 Parameters
24.04
Minimum torq ref
Defines the minimum torque reference.
-1000.0 … 0.0%
Minimum torque reference.
10 = 1%
24.05
Load share
Scales the torque reference to a required level (torque
reference is multiplied by the selected value).
-8.000 … 8.000
Torque reference scaling.
1000 = 1
24.06
Torq ramp up
Defines the torque reference ramp-up time, i.e. the time for
the reference to increase from zero to the nominal motor
torque.
0.000 … 60.000 s
Torque reference ramp-up time.
1000 = 1 s
24.07
Torq ramp down
Defines the torque reference ramp-down time, i.e. the time for
the reference to decrease from the nominal motor torque to
zero.
0.000 … 60.000 s
Torque reference ramp-down time.
1000 = 1 s
25
25 Critical speed
Sets up critical speeds, or ranges of speeds, that are avoided
due to, for example, mechanical resonance problems.
25.01
Crit speed sel
Enables/disables the critical speeds function.
Example:
A fan has vibrations in the range of 540 to 690 rpm
and 1380 to 1560 rpm. To make the drive to jump over the
vibration speed ranges:
• activate the critical speeds function,
• set the critical speed ranges as in the figure below.
Disable
Critical speeds are disabled.
0
Enable
Critical speeds are enabled.
1
No.
Name/Value
Description
FbEq
540
690
1380
1560
1
= 540 rpm
2
= 690 rpm
3
= 1380 rpm
4
= 1590 rpm
1
2
3
4
Motor speed
(rpm)
Drive speed
(rpm)
Drive speed
(rpm)
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 2: ......
Page 4: ......
Page 24: ...24 Start up...
Page 28: ...28 Control locations and operating modes...
Page 252: ...252 Fieldbus control...