Parameters 215
Activates the variable slope function, which controls the slope
of the speed ramp during a speed reference change. This
allows for a constantly variable ramp rate to be generated,
instead of just the standard two ramps normally available.
If the update interval of the signal from an external control
system and the variable slope rate (
are equal, speed reference (
) is
a straight line.
This function is only active in remote control.
Off
Variable slope disabled.
0
On
Variable slope enabled (not available in local control).
1
Defines the rate of the speed reference change when variable
slope is enabled by parameter
For the best result, enter the reference update interval into
this parameter.
50 ms
2…30000 ms
Variable slope rate.
1 = 1 ms
No.
Name/Value
Description
Def/FbEq16
t
Speed
reference
Speed reference
Time
A
t = update interval of signal from an external control system
A = speed reference change during t
ACS580 FW.book Page 215 Wednesday, September 21, 2016 9:48 PM