176 Parameters
Start inhibit status word. This word specifies the source of the
inhibiting signal that is preventing the drive from starting.
The conditions marked with an asterisk (*) only require that
the start command is cycled. In all other instances, the
inhibiting condition must be removed first.
See also parameter
, bit 1.
This parameter is read-only.
0b0000
0b0000...0b1111
Start inhibit status word.
1 = 1
Speed control status word.
This parameter is read-only.
0b0000
0b0000...0b1111
Speed control status word.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Not ready run
1 = DC voltage is missing or drive has not been parametrized
correctly. Check the parameters in groups 95 and 99.
1
Ctrl location changed
* 1 = Control location has changed.
2
SSW inhibit
1 = Control program is keeping itself in inhibited state.
3
Fault reset
* 1 = A fault has been reset.
4
Lost start enable
1 = Start enable signal missing.
5
Lost run enable
1 = Run enable signal missing.
6
Reserved
7
STO
1 = Safe torque off function active.
8
Current calibration
ended
* 1 = Current calibration routine has finished.
9
ID run ended
* 1 = Motor identification run has finished.
10
Reserved
11
Em Off1
1 = Emergency stop signal (mode off1).
12
Em Off2
1 = Emergency stop signal (mode off2).
13
Em Off3
1 = Emergency stop signal (mode off3).
14
Auto reset inhibit
1 = The autoreset function is inhibiting operation.
15
Jogging active
1 = The jogging enable signal is inhibiting operation.
Bit
Name
Description
0
Zero speed
1 = Drive has been running below zero speed limit (par.
)
for a time defined by parameter
.
1
Forward
1 = Drive is running in forward direction above zero speed limit
(par.
).
2
Reverse
1 = Drive is running in reverse direction above zero speed limit
(par.
).
3…6
Reserved
7
Any constant speed
request
1 = A constant speed or frequency has been selected; see par.
8…15
Reserved
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...