ACS550 User’s Manual
261
Technical data
Ratings, 500…600 V drives
Abbreviated column headers are described in section
on page
Symbols
Sizing
The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current. Also note that:
• the ratings apply for ambient temperature of 40 °C (104 °F)
• the maximum allowed motor shaft power is limited to 1.5 ·
P
hd
.
If the limit is
exceeded, motor torque and current are automatically restricted. The function
protects the input bridge of the drive against overload.
Type code
Normal use
Heavy-duty use
Frame
size
ACS550-U1-
see below
I
2N
A
P
N
kW
P
N
hp
I
2hd
A
P
hd
kW
P
hd
hp
Three-phase supply voltage,
500
…
600 V
(Note 1)
-02A7-6
2.7
1.5
2
2.4
1.1
1.5
R2
-03A9-6
3.9
2.2
3
2.7
1.5
2
R2
-06A1-6
6.1
4
5
3.9
2.2
3
R2
-09A0-6
9.0
5.5
7.5
6.1
4
5
R2
-011A-6
11
7.5
10
9.0
5.5
7.5
R2
-017A-6
17
11
15
11
7.5
10
R2
-022A-6
22
15
20
17
11
15
R3
-027A-6
27
18.5
25
22
15
20
R3
-032A-6
32
22
30
27
18.5
25
R4
-041A-6
41
30
40
32
22
30
R4
-052A-6
52
37
50
41
30
40
R4
-062A-6
62
45
60
52
37
50
R4
-077A-6
77
55
75
62
45
60
R6
-099A-6
99
75
100
77
55
75
R6
-125A-6
125
90
125
99
75
100
R6
-144A-6
144
110
150
125
90
125
R6
00467918.xls B
1. Not available in ACS550-01 series.
Typical ratings:
Normal use
(10% overload capability)
I
2N
continuous rms current. 10% overload is allowed for one minute in ten minutes.
P
N
typical motor power in normal use. The kilowatt power ratings apply to most IEC, 4-pole
motors. The horsepower ratings apply to most 4-pole NEMA motors.
Heavy-duty use
(50% overload capability)
I
2hd
continuous rms current. 50% overload is allowed for one minute in ten minutes.
P
hd
typical motor power in heavy duty use. The kilowatt power ratings apply to most IEC, 4-pole
motors. The horsepower ratings apply to most 4-pole NEMA motors.
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...