ACS550 User’s Manual
Embedded fieldbus
– Actual value 3
– Actual value 4
– Actual value 5
– Actual value 6
– Actual value 7
– Actual value 8
The content of these words is defined by profiles. For details on the profiles used,
sees section
ABB control profiles technical data
.
Note:
The words “output” and “input” are used as seen from the fieldbus controller
point of view. For example an output describes data flow from the fieldbus controller
to the drive and appears as an input from the drive point of view.
Planning
Network planning should address the following questions:
• What types and quantities of devices must be connected to the network?
• What control information must be sent down to the drives?
• What feedback information must be sent from the drives to the controlling
system?
Mechanical and electrical installation – EFB
WARNING!
Connections should be made only while the drive is disconnected from
the power source.
Drive terminals 28
…
32 are for RS485 communications.
• Use Belden 9842 or equivalent. Belden 9842 is a dual twisted, shielded pair cable
with a wave impedance of 120 ohm.
• Use one of these twisted shielded pairs for the RS485 link. Use this pair to
connect all A (-) terminals together and all B (+) terminals together.
• Use one of the wires in the other pair for the logical ground (terminal 31), leaving
one wire unused.
• Do not directly ground the RS485 network at any point. Ground all devices on the
network using their corresponding earthing terminals.
• As always, the grounding wires should not form any closed loops, and all the
devices should be earthed to a common ground.
• Connect the RS485 link in a daisy-chained bus, without dropout lines.
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...