150
ACS550 User’s Manual
Group 35: MOTOR TEMP MEAS
This group defines the detection and reporting for a particular potential fault – motor
overheating, as detected by a temperature sensor. Typical connections are defined
below.
WARNING!
IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either non-
conductive or conductive but not connected to the protective earth.
To fulfil this requirement, connect a thermistor (and other similar components) to the
drive’s control terminals using any of these alternatives:
• Separate the thermistor from live parts of the motor with double reinforced
insulation.
• Protect all circuits connected to the drive’s digital and analog inputs. Protect
against contact, and insulate from other low voltage circuits with basic insulation
(rated for the same voltage level as the drive’s main circuit).
• Use an external thermistor relay. The relay insulation must be rated for the same
voltage level as the drive’s main circuit.
The figure below shows alternate thermistor connections. At the motor end the cable
shield should be earthed through a 10 nF capacitor. If this is not possible, leave the
shield unconnected.
Motor
T
10 nF
Motor
T
T
T
One sensor
Three sensors
10 nF
AI
1
AGND
AO
1
AGND
AI
1
AGND
AO
1
AGND
Motor
T
10 nF
Motor
T
Thermistor
relay
Control board
DI6
+24 V DC
Control board
DI6
+24 V DC
Thermistor relay:
THERM
(0) or
THERM
(1)
THERM
(0)
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...