108
ACS510 User’s Manual
Start-Up
Group 34: Panel Display Process Variables
This group defines the content for control panel display (middle area), when the
control panel is in the Output mode.
Code Description
3401
SIGNAL1 PARAM
Selects the first parameter (by number) displayed on the control panel.
• Definitions in this group define display content when the control panel is in
the control mode.
• Any Group 01 parameter number can be selected.
• Using the following parameters, the display value can be scaled, converted
to convenient units, and/or displayed as a bar graph.
• The figure identifies selections made by parameters in this group.
100 = not selected – First parameter not displayed.
101…159 = Displays parameter 0101…0159. If parameter does not exist, the display shows “n.a.”
3402
SIGNAL1 MIN
Defines the minimum expected value for the first display parameter.
Use parameters 3402, 3403, 3406, and 3407, for example to convert
a Group 01 parameter, such as 0102
SPEED
(in rpm) to the speed of a
conveyor driven by the motor (in ft/min). For such a conversion, the
source values in the figure are the min. and max. motor speed, and
the display values are the corresponding min. and max. conveyor
speed. Use parameter 3405 to select the proper units for the display.
Note! Selecting units does not convert values. Parameter is not
effective if parameter 3404
OUTPUT1 DSP FORM
= 9 (
DIRECT
).
3403
SIGNAL1 MAX
Defines the maximum expected value for the first display parameter.
Note: Parameter is not effective if parameter 3404
OUTPUT1 DSP
FORM
= 9 (
DIRECT
).
3404
OUTPUT1 DSP FORM
Defines the decimal point location for the first display parameter.
0…7 – Defines the decimal point location.
• Enter the number of digits desired to the right of the decimal
point.
• See the table for an example using pi (3.14159).
8 =
BAR
METER
– Specifies a bar meter display.
9 =
DIRECT
– Decimal point location and units of measure are
identical to the source signal. See Group 01 parameter listing in
“Complete Parameter List” for resolution (which indicates the
decimal point location) and the units of measure.
3405
OUTPUT1 UNIT
Selects the units used with the first display parameter. Parameter is not effective if parameter 3404
OUTPUT1 DSP
FORM
= 9 (
DIRECT
).
P 0137
P 0138
P 0139
P 3404 P 3405
Source Value
P 3407
P 3406
P 3403
P3402
Display
Value
3404 Value
Display
Range
0
+ 3
-32768…+32767
(Signed)
1
+ 3.1
2
+ 3.14
3
+ 3.142
4
3
0…65535
(Unsigned)
5
3.1
6
3.14
7
3.142
0 =
NO
UNIT
9 = °C
18 = MWh
27 = ft
36 = l/s
45 = Pa
54 = lb/m
63 = Mrev
1 = A
10 = lb ft
19 = m/s
28 = MGD
37 = l/min
46 = GPS
55 = lb/h
64 = d
2 = V
11 = mA
20 = m
3
/h
29 = inHg
38 = l/h
47 = gal/s
56 = FPS
65 = inWC
3 = Hz
12 = mV
21 = dm
3
/s
30 = FPM
39 = m
3
/s
48 = gal/m
57 = ft/s
66 = m/min
4 = %
13 = kW
22 = bar
31 = kb/s
40 = m
3
/m
49 = gal/h
58 = inH
2
O
67 = Nm
5 = s
14 = W
23 = kPa
32 = kHz
41 = kg/s
50 = ft
3
/s
59 = in wg
6 = h
15 = kWh
24 = GPM
33 = Ohm
42 = kg/m
51 = ft
3
/m
60 = ft wg
7 = rpm
16 = °F
25 = PSI
34 = ppm
43 = kg/h
52 = ft
3
/h
61 = lbsi
8 = kh
17 = hp
26 = CFM
35 = pps
44 = mbar
53 = lb/s
62 = ms
The following units are useful for the bar diaplay.
117 = %ref
119 = %dev 121 = % SP 123 = Iout
125 = Fout
127 = Vdc
118 = %act
120 = % LD 122 = %FBK 124 = Vout
126 = Tout