Fault tracing
23
000D (Permanent magnet motors
only)
Second acceleration did not
finish within reasonable time.
Contact your local ABB representative.
000E…0010 Internal error.
Contact your local ABB representative.
0011 (Synchronous reluctance
motors only)
Pulse test error.
Contact your local ABB representative.
0012 Motor too large for advanced
standstill ID run.
Check that the motor and drive sizes are
compatible.
Contact your local ABB representative.
0013 (Asynchronous motors only)
Motor data error.
Check that the motor nominal value
settings in the drive are the same as in
the motor nameplate.
Contact your local ABB representative.
FF63
STO diagnostics
failure.
SW internal malfunction.
Reboot the control unit (using parameter
96.08
Control board boot
) or by cycling
power.
FF81
FB A force trip
A fault trip command has been
received through fieldbus
adapter A.
Check the fault information provided by
the PLC.
FF8E
EFB force trip
A fault trip command has been
received through the
embedded fieldbus interface.
Check the fault information provided by
the PLC.
Code
(hex)
Fault / Aux. code
Cause
What to do