66 Electrical installation
Connection procedure
WARNING!
Obey the instructions in chapter
on page
you ignore them, injury or death, or damage to the equipment can occur.
WARNING!
If the drive is connected to an IT (non-grounded) system or to a
corner-grounded TN system, disconnect the EMC filter grounding screw.
If the drive is connected to an IT (non-grounded) system, disconnect the
varistor grounding screw.
Before you start the work, stop the drive and do the steps in
on page
.
For information on cable routing, refer to
on page
For information on correct torques, refer to
Terminal data for the power cables
on
1. Strip the motor cable.
2. Ground the motor cable shield under the
grounding clamp.
3. Twist the motor cable shield into a bundle,
put yellow-green insulation tape on it, fit a
Summary of Contents for ACS380 Series
Page 1: ...ABB MACHINERY DRIVES ACS380 drives Hardware manual...
Page 4: ......
Page 12: ...12 Table of contents...
Page 20: ...20 Safety instructions...
Page 46: ...46 Mechanical installation...
Page 60: ...60 Planning the electrical installation...
Page 86: ...86 Maintenance...
Page 120: ...120 Technical data...
Page 122: ...122 Dimension drawings Frame R0 1 phase 230 V...
Page 123: ...Dimension drawings 123 Frame R0 400 V...
Page 124: ...124 Dimension drawings Frame R1 230 V...
Page 125: ...Dimension drawings 125 Frame R1 3 phase 230 V and 3 phase 400 V...
Page 126: ...126 Dimension drawings Frame R2 230 V...
Page 127: ...Dimension drawings 127 Frame R2 400 V...
Page 128: ...128 Dimension drawings Frame R3 400 V...
Page 129: ...Dimension drawings 129 Frame R4 400 V...
Page 130: ...130 Dimension drawings...
Page 138: ...138 Resistor braking...
Page 169: ...BTAC 02 pulse encoder interface module 169 Dimensions 3AXD50000031154 rev A...