Planning the electrical installation 55
Routing the cables
Select the cable routes as follows:
• Put the input power cable (I), motor
cable (M) and control cables (C) into
separate trays.
• Put the motor cable (M) away from
the other cables.
• Make sure that there is a minimum of
200 mm between the input power
cable (I) and the control cables (C).
• Make sure that there is a minimum of
500 mm between the motor cable (M)
and the control cables (C).
• Make sure that there is a minimum
300 mm between the input power
cable (I) and the motor cable (M).
• If the control cables cross the input
power or motor cables, put the cables
at 90 degrees to each other.
• You can put several motor cables in
parallel.
• Do not install other cables in parallel
with the motor cables.
• Make sure that the cable trays are
electrically bonded to each other and
to the electrical ground.
• Make sure that the control cables are appropriately supported outside the drive to
relieve stress on the cables.
• Make sure that there are no sources of strong magnetic fields such as high-
current single-core conductors or contactor coils near the drive. A strong
magnetic field can cause interference or inaccuracy in the operation of the drive. If
there is interference, move the source of the magnetic field away from the drive.
I
C
M
Summary of Contents for ACS380 Series
Page 1: ...ABB MACHINERY DRIVES ACS380 drives Hardware manual...
Page 4: ......
Page 12: ...12 Table of contents...
Page 20: ...20 Safety instructions...
Page 46: ...46 Mechanical installation...
Page 60: ...60 Planning the electrical installation...
Page 86: ...86 Maintenance...
Page 120: ...120 Technical data...
Page 122: ...122 Dimension drawings Frame R0 1 phase 230 V...
Page 123: ...Dimension drawings 123 Frame R0 400 V...
Page 124: ...124 Dimension drawings Frame R1 230 V...
Page 125: ...Dimension drawings 125 Frame R1 3 phase 230 V and 3 phase 400 V...
Page 126: ...126 Dimension drawings Frame R2 230 V...
Page 127: ...Dimension drawings 127 Frame R2 400 V...
Page 128: ...128 Dimension drawings Frame R3 400 V...
Page 129: ...Dimension drawings 129 Frame R4 400 V...
Page 130: ...130 Dimension drawings...
Page 138: ...138 Resistor braking...
Page 169: ...BTAC 02 pulse encoder interface module 169 Dimensions 3AXD50000031154 rev A...